RC-1170/1270 Redundancy Switch Controllers
Revision 0
Front Panel Operation
3–6
MN-RC-1170/1270
Select: Config: Unit: Common: Current Window Menu
Table 3-6. Select: Config: Unit: Common: Current Window Menu Description
Item
Description
Enable
Use to turn off/on Enable feature.
Range
Use to select the Range percent.
If measured current varies by more than ± x%, as shown in the Range percent setting, an
issue will be identified with the unit.
Use the
◄ ►
arrow keys to select Enable or Range. Press ENTER to continue.
Select: Config: Unit: Unit 1/2/3 Menu
Table 3-7. Select: Config: Unit: Unit 1/2/3 Window Screen
Menu Branch
Function
Current Source
Select Off, 13 V, 18 V. via up/down key press
This can only be changed if the rear panel Bias Control Switch is in the center
position.
Ref
This shows the nominal current as recorded by Calibrate in this screen or as
recorded by the rear panel Calibrate push button.
Calibrate
There is a calibrated reference point for both 13 V and 18 V. Select this and press
“Enter” to set calibration point.