5-1. User Logic Input #1 Enable (Event Macros 07 and 08)
When the box is checked, a transition from low to high on connector J1-1 will execute event macro #07
while a transition from high to low will execute event macro #08.
5-2. User Logic Input #2 Enable (Event Macros 09 and 10)
When the box is checked, a transition from low to high on connector J1-2 will execute event macro #09
while a transition from high to low will execute event macro #10.
5-3. User Logic Input #3 Enable (Event Macros 11 and 12)
When the box is checked, a transition from low to high on connector J1-21 will execute event macro
#11 while a transition from high to low will execute event macro #12.
5-4. User Logic Input #4 Enable (Event Macros 13 and 14)
When the box is checked, a transition from low to high on connector J1-22 will execute event macro
#13 while a transition from high to low will execute event macro #14.
5-5. User Logic Input #5 Enable (Event Macros 15 and 16)
When the box is checked, a transition from low to high on connector J1-24 will execute event macro
#15 while a transition from high to low will execute event macro #16.
6-1. USER Output Switch #1 Enable
When this box is checked, switch #1 will perform per its pre-defined function. Connector J1-14 or J2-6
will sink 150 MA to ground. At default this switch is defined as a remote controlled switch and is
controlled by user macros 10 and 11. To turn switch #1 on go to the START PAGE and enter 10 in the
Execute User Macro box and click the EXECUTE button. To turn Switch #1 off enter 11 in the box and
click EXECUTE.
6-2. USER Output Switch #2 Enable
When this box is checked, switch #2 will perform per its pre-defined function. Connector J1-15 or J2-7
will sink 150 MA to ground. At default this switch is defined as a remote controlled switch and is
controlled by user macros 12 and 13. To turn switch #2 on go to the START PAGE and enter 12 in the
Execute User Macro box and click the EXECUTE button. To turn Switch #2 off enter 13 in the box and
click EXECUTE.
6-3. USER Output Switch #3 Enable
When this box is checked, switch #3 will perform per its pre-defined function. Connector J1-19 or J2-6
will sink 150 MA to ground. At default this switch is defined as a remote controlled switch and is
controlled by user macros 14 and 15. To turn switch #3 on go to the START PAGE and enter 14 in the
Execute User Macro box and click the EXECUTE button. To turn Switch #3 off enter 15 in the box and
click EXECUTE.
6-4. USER Output Switch #4 Enable
When this box is checked, switch #4 will perform per its pre-defined function. Connector J1-20 or J2-7
will sink 150 MA to ground. At default this switch is defined as a remote controlled switch and is
controlled by user macros 16 and 17. To turn switch #4 on go to the START PAGE and enter 16 in the
Execute User Macro box and click the EXECUTE button. To turn Switch #4 off enter 17 in the box and
click EXECUTE.
6-5. USER Output Switch #5 Enable
When this box is checked, switch #5 will perform per its pre-defined function. Connector J1-5 will sink
150 MA to ground. At default this switch is defined as a remote controlled switch and is controlled by
user macros 18 and 19. To turn switch #5 on go to the START PAGE and enter 18 in the Execute User
Macro box and click the EXECUTE button. To turn Switch #5 off enter 19 in the box and click EXECUTE.
Содержание CAT-800
Страница 42: ...5 13 3634 SET PORT 3 CTCSS LOGIC COR OR CTCSS ACTIVE LO...
Страница 87: ...11 1 Chapter 11 Drawings CAT 800 Repeater Controller Board...
Страница 88: ...11 2 DR 800 Digital Audio Player...
Страница 90: ...12 2 CAT 800 Sheet 1 of 4...
Страница 91: ...12 3 CAT 800 Sheet 2 of 4...
Страница 92: ...12 4 Sheet 3 of 4...
Страница 93: ...12 5 Sheet 4 of 4...
Страница 94: ...12 6 DR 800 Digital Audio WAV Player Sheet 1 of 1...