If you need to…
You should…
Confirm the other end of a connection
between two iPatch panel ports.
Locate the unknown end of the patch cord. Then press and hold the unknown port’s
button for 2 seconds.
Complete the connection to an iPatch
panel port.
Insert the other end of the patch cord. If the connection information on the display is
correct, press Yes.
Confirm the other end of a simplex
fiber connection between 2 iPatch
panel ports for a known port (and
both positions for the port to be
confirmed are in use.)
1.
Select a port to be confirmed from the confirms list.
2.
If confirming a fiber port, and the two strands of that port are patched to different
endpoints, press the “simplex” button, and then use the A/B toggle button to choose
whether the B or A strand is to be confirmed.
3.
Locate the far end of the patch cord being confirmed, and then press and hold the trace
button above that port.
4.
If the port where the cord terminates is a fiber port, both strands of the port are populated
and the patch being confirmed is a simplex connection, the system will ask which of the two
strands is the strand being selected. Use the A/B toggle button to choose whether the B or A
strand is the far end of the patch being confirmed. When the correct connection is displayed,
press Yes.
Complete the connection to equipment.
Press and hold the iPatch panel port’s button for 2 seconds, or press the
Equipment
button on
the imVision Controller X display.
Remove the connection.
Remove both ends of the patch cord.
Multi-Rack Mode
A single imVision Controller X can manage up to 3 racks at one time.
The 2 dependent racks an imVision Controller X can manage must be to the immediate left and right of the rack containing
the imVision Controller X. Use the extended-length cables and panel buses in the Rack Extender Kit (760237879) to connect
to dependent racks.
In multi-rack mode, the quantity of iPatch panels that the rack can manage is limited to 10 rack units per rack.
imVision Controllers are not compatible in a zone using Multi-Rack Mode.