ComfortFlame.us.com
900568-00E
15
Figure 22 - Equipment Shutoff Valve
Open
Closed
Equipment
Shutoff Valve
Figure 24 - Checking Gas Joints for Propane/LP Gas
Figure 23 - Checking Gas Joints for Natural Gas
Gas Control Valve
Equipment
Shutoff Valve
Gas Meter
Equipment Shutoff Valve
Gas Control Valve
Propane/LP
Supply Tank
INSTALLATION
Continued
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect fireplace with its appliance main gas valve (control
valve) and equipment shutoff valve from gas supply piping system.
Pressures in excess of 1/2 psig will damage fireplace regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was
connected.
3. Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas or opening main gas valve
located on or near gas meter for natural gas or using compressed
air.
4. Check all joints of gas supply piping system. Apply noncorrosive
leak detection fluid to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect fireplace and equipment shutoff valve to gas supply.
Check reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve
(see
Figure 22
)
.
2. Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas or opening main gas valve
located on or near gas meter for natural gas or using compressed
air.
3. Check all joints from gas meter to equipment shutoff valve for natural
gas or propane/LP supply to equipment shutoff valve for propane/
LP
(see
Figures 23 or 24
).
Apply noncorrosive leak detection fluid
to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
PRESSURE TESTING FIREPLACE GAS CONNECTIONS
1. Open equipment shutoff valve
(see
Figure 22
).
2. Open main gas valve located on or near gas meter for natural gas
or open propane/LP supply tank valve.
3. Make sure control knob of fireplace is in the OFF position.
4. Check all joints from equipment shutoff valve to gas control valve
(see
Figures 23 or 24
)
. Apply noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light fireplace
(see Operation,
Page 18
).
Check all other internal
joints for leaks.
7. Turn off fireplace
(see To Turn Off Gas to Appliance,
Page 19
).
The appliance and its appliance main gas valve must be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures
in excess of
1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system
by closing its equipment shutoff valve during any pressure testing of
the gas supply piping system at test pressures
equal to or less than
1/2 psi (3.5 kPa).
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM