ComfortFlame.us.com
900568-00E
9
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Top 42"; Left and Bottom 16"; Right
Side and Rear 0"; Front 36"
Figure 6 - Assembling Trim
Trim
Hanging
Screws
Assembled
Trim
Hanging
Notches on
Trim
Figure 7 - Attaching Trim to Fireplace
*
Example
Figure 8 - Minimum Clearance for Combustible to Wall
*Minimum 16" from Side Wall
Side Trim
Slot
Mitered
Edge
Slot
Shim
Set Screws
Adjusting
Plate
Top Trim
ASSEMBLING AND ATTACHING BLACK TRIM
IMPORTANT:
If you are recessing the firebox in a wall, do not attach
trim at this time. See
Page 12
.
NOTE:
The instructions below show assembling and attaching trim
to fireplace.
1. Remove packaging from 3 pieces of trim.
2. Locate 2 adjusting plates with set screws and 2 shims in the
hardware packet.
3. Align shim under adjusting plate as shown in
Figure 6
.
4. Slide one end of adjusting plate/shim in slot on mitered edge of
top trim
(see
Figure 6
).
5. Slide other end of adjusting plate/shim in slot on mitered edge of
side trim
(see
Figure 6
)
.
6. While firmly holding edges of trim together, tighten both set
screws on the adjusting plate with slotted screwdriver.
7. Repeat steps 1 through 6 for other side.
8. Tighten trim hanging screws (#10 x 6.25 shoulder) into holes in
cabinets. Place assembled trim onto fireplace cabinet. Align hang-
ing notches on trim with hanging screws on side of fireplace
(see
Figure 7
).
Push trim firmly into place, sliding hanging notches
over hanging screws.
INSTALLATION
Continued
Maintain adequate clearances for accessibility for purposes
of servicing and proper operation.
WARNING: Maintain the minimum clearances. If
you can, provide greater clearances from floor, ceiling
and adjoining wall.
INSTALLATION CLEARANCES
Carefully follow the instructions below. This will ensure safe instal-
lation.
Minimum Clearances For Side Combustible Material, Side Wall
and Ceiling
A. Clearances from the side of the fireplace cabinet to any combustible
material and wall should follow diagram in
Figure 8
.
Example:
The face of a mantel, bookshelf, etc. is made of combustible
material and protrudes 3-1/2" from the wall. This combustible material
must be 4" from the side of the fireplace opening
(see
Figure 8
).
B. Clearances from the top of the fireplace opening to the ceiling should
not be less than 42".