Comelit ZSP100 Series Скачать руководство пользователя страница 7

 

OPERATION 

1 NORMAL 

Battery test 

Power supply 
test 

Front cover LED status 

230 VAC 

Green LED 

On 

Flashing 

On 

ALARM 

Yellow LED 

Off 

On 

On 

Board LED status 

MAINS 

Green LED 

On 

Off 

On 

BATTERY 

Yellow LED 

Off 

Off 

Flashing 

RELAY status 

MAINS FLT 

Power supply fault 

Activated 

In standby 

Activated 

GEN FLT 

General fault 

Activated 

In standby 

In standby 

 

*) If the battery is disconnected for over 30 minutes, the BAT diode will remain lit steadily. 
 

Check whether the GEN FLT fault indication has been transmitted correctly during the tests. 

Caution

 do not connect the negative pole of the battery (B) to the negative pole OUT1 OUT2 (-). 

When mains power is being supplied, the battery voltage is over 21.6 V.  
The Warning indication (brief flashes of the ALARM LED) is displayed with intermediate voltages.  
In battery operating mode, when there is no primary (230 V) power supply and the value drops below 21 V, the LVDD (Low 
Voltage Disconnect Device) disconnects the battery to avoid damaging it. 
 

LED indication (power supply unit front door): 

 

230 V

 

Green LED

 

0 Off

 

No mains, battery disconnected

 

1 On

 

Mains power supply present, power supply unit / battery charger operative

 

0/1 Flashing

 

Battery operation:

 

charger power supply faulty *1)

 

Alarm

 

Yellow LED

 

0 Off

 

Working ok

 

1 On

 

Battery operation:

 

faulty power supply

 

-

 

No battery, or the voltage of the battery connected is under 10 V -

 

-

 

Battery circuit fuse resistance too high (> 250 mΩ)

 

-

 

Output fuse blown

 

-

 

Battery voltage under 22 V with mains power supply present *1)

 

0/1 fast flashing

 

External alarm or internal alarm (tamper)

 

0/1 slow

 

flashing

 

battery recognised (U> 10 V), but the voltage is too low (U <21.6 V)

 

 

*1) The status may emerge when the mains power supply has been restored and when the battery begins recharging. 

 

LED indication on the power supply board: 

 

0 Off

 

No mains power supply

 

1 On

 

Mains power supply present, power supply unit / battery charger operative

 

0/1 

fast flashing 

Mains power supply present, power supply unit / battery charger faulty *1)

 

0 Off

 

Battery working

 

1 or 0/1 slow flashing 

Battery circuit resistance > 250 mΩ (including no battery or

 

blown battery fuse *1)

 

*1) The battery circuit resistance values are checked, including battery and fuse disconnection, every 10 minutes. After the 
fault has been detected three times, the BAT LED lights up steadily and the GEN FLT relay indication is activated at the same 
time. 

 

Relay indication (0 - relay de-energised, 1 - relay energised) 

 

Mains FLT

 

Power supply fault 

0 Off

 

No 230 V main power supply

 

1 On

 

Electricity mains present, power supply unit / battery charger working

 

GEN FLT

 

General fault 

0 Off

 

Alarm LED flashing *1), *2)

 

1 On

 

All ok

 

 

*1) Power supply / charger fault

 

*2) After an electricity mains supply fault and after the power has been restored, the indication is activated with a delay of 5s. 

Содержание ZSP100 Series

Страница 1: ...NTATION SUPPL MENTAIRE EXTRA VOEDINGSEENHEID ZSP100 Alimentatore per Sistemi rivelazione incendio Conforme Norma EN 54 4 1997 A1 2002 A2 2006 2 Certificato di conformit CNBOP No 1438 CPD 0163 Certific...

Страница 2: ...CARICA BATTERIE DIMENSIONI ZSP100 2 5A 18 2 5 A 1 0 A 7 20Ah 395x356x96mm ZSP100 5 5A 18 5 5 A 1 0 A 7 20Ah 395x356x96mm Fig 1 Vista frontale e laterale dell alimentatore Gli alimentatori nella parte...

Страница 3: ...scita Guasto Generale Se si vuole utilizzare il tamper apertura portella collegare un contatto NC sul connettore Z204 in caso contrario lasciare il jumper chiuso default B201 FUSIBILE circuito di rete...

Страница 4: ...di batteria collegata inferiore a 10 V Resistenza del fusibile del circuito della batteria troppo alta 250m Fusibile uscita bruciato Tensione della batteria al di sotto di 22V con l alimentazione di...

Страница 5: ...r wall mounting TECHNICAL CHARACTERISTICS POWER SUPPLY UNIT MAX CURRENT OUTPUT LOAD CURRENT BATTERIES DIMENSIONS ZSP100 2 5 A 18 2 5 A 1 0 A 7 20 Ah 395x356x96 mm ZSP100 5 5 A 18 5 5 A 1 0 A 7 20 Ah 3...

Страница 6: ...fault indication and the switching of the General Fault output relay If you want to use the door opening tamper connect an NC contact on connector Z204 otherwise leave the jumper closed default B201...

Страница 7: ...supply No battery or the voltage of the battery connected is under 10 V Battery circuit fuse resistance too high 250 m Output fuse blown Battery voltage under 22 V with mains power supply present 1 0...

Страница 8: ...ll es en saillie CARACT RISTIQUES TECHNIQUES ALIMENTATION COURANT MAXI DE SORTIE COURANT DE CHARGE BATTERIES DIMENSIONS ZSP100 2 5A 18 2 5 A 1 0 A 7 20 Ah 395x356x96mm ZSP100 5 5A 18 5 5 A 1 0 A 7 20...

Страница 9: ...jaune allum e et l change du relais de sortie Panne G n rale Pour utiliser l autoprotection d ouverture du volet brancher un contact NF sur le connecteur Z204 Dans le cas contraire laisser le cavalier...

Страница 10: ...ou la tension de la batterie connect e est inf rieure 10 V R sistance du fusible du circuit de la batterie trop lev e 250 m Fusible de sortie grill Tension de la batterie inf rieure 22 V en pr sence d...

Страница 11: ...alimentadores se han dise ado para montarse en la pared CARACTER STICAS T CNICAS ALIMENTADOR SALIDA EN CORRIENTE M X CORRIENTE DE CARGA BATER AS DIMENSIONES ZSP100 2 5 A 18 2 5 A 1 0 A 7 20 Ah 395x35...

Страница 12: ...marillo y el intercambio del rel de salida de aver a general Si se desea utilizar el tamper de apertura de la tapa conectar un contacto normalmente cerrado al conector Z204 en caso contrario dejar el...

Страница 13: ...imentaci n defectuosa Ninguna bater a o la tensi n de la bater a conectada es inferior a 10 V Resistencia del fusible del circuito de la bater a demasiado alta 250 m Fusible de la salida fundido Tensi...

Страница 14: ...e TECHNISCHE EIGENSCHAPPEN VOEDINGSEENHEID MAX UITGANGSSPANNING LAADSTROOM BATTERIJEN AFMETINGEN ZSP100 2 5A 18 2 5 A 1 0 A 7 20Ah 395x356x96mm ZSP100 5 5A 18 5 5 A 1 0 A 7 20Ah 395x356x96mm Fig 1 Fro...

Страница 15: ...ais Algemene storingsuitgang Als u de tamper opening frontpaneel wilt gebruiken sluit dan een NC contact aan op de connector Z204 Zo niet laat de jumper dan gesloten default Indicatie zekeringen B201...

Страница 16: ...spanning van de aangesloten batterij is lager dan 10 V De zekeringsweerstand van het circuit van de batterij is te hoog 250m Uitgangszekering verbrand Batterijspanning lager dan 22V terwijl de netvoe...

Страница 17: ...Comelit Group Spa Via Don Arrigoni 5 24020 Rovetta S Lorenzo Italy Tel 39 0 346 750011 Fax 39 0 346 71436 www comelitgroup com...

Отзывы: