Thermostat description
: enter a description of the climate zone which appears on the supervisor.
Winter/Summer status output
: this
fi
eld indicates the module number and the output number to control in order to make the
Mintouch switch automatically between winter and summer modes. If the output is inactive, winter operating mode will be set; if the
output is activated, on the other hand, summer operating mode will be set.
Zone for Day / Night / Empty set
: a zone number can be assigned to one of the 3 day, night or empty setpoints. This means it is
possible, by closing a digital input for example, to select the same setpoint on all thermostats or Minitouch units in the system.
Zone for Winter / Summer set
: a zone number can be assigned to one of the 2 summer or winter setpoints. This means it is possible,
by closing a digital input for example, to set the same mode on all thermostats or Minitouch units in the system.
Interval
: indicates the time in seconds required to send setpoints and temperature settings entered on the Minitouch over the BUS.
These transmissions update the supervisors as to the status of the Minitouch (e.g. temperature readings). We recommend leaving
this entry set to the default value (5 minutes).
Delta
: indicates the thermostat output activation interval, in tenths of a degree. For example, if this is set to 4 tenths of a degree
(default value) and the thermostat is set to 20°C in winter day mode, it will activate the relay until the temperature of 20°C is reached.
After switching off, it will be reactivated when the temperature drops below 19.6°C (20°C - 0.4°C). In summer mode, operation is
reversed and therefore if a setpoint of 20°C is selected, the thermostat will activate cooling mode until the temperature drops to 20°C.
After switching off, it will be reactivated when the temperature exceeds 20.4°C.
Correction
: this value, in tenths of a degree, can be used to adjust the measuring process for the on-board temperature sensor, if
installed in speci
fi
c conditions, e.g. near draughts, or in
fl
ush-mounted boxes which are especially cool.
For example, if the sensor on board the Minitouch records a temperature of 18.8°C but the actual temperature of the room is 19.0°C,
this value can be set to 2. This means the displayed temperature will always be 0.2°C above the value measured by the sensor.
Speed 1-2 1-3 Delta
: these values, in tenths of a degree, indicate the temperature difference, in relation to the selected setpoint,
required for activation of speed level 2 or speed level 3 in fan coil mode. If using a 3-speed convector heater, you can adjust these 3
speed levels according to the set and measured temperatures.
For example, if the temperature is set to 22°C with default values of 10 and 20, the convector heater will be activated at speed level 1
3.5.4 - CONFIGURING A MINITOUCH THERMOSTAT
82
Содержание simplehome
Страница 1: ...www comelitgroup com EN TECHNICAL MANUAL Technical manual for the SimpleHome system...
Страница 35: ...Fastening Unfastening Sensor mounting 35...
Страница 41: ...150 cm 120 cm Minitouch timer thermostat mounting 41...
Страница 43: ...Planux Manager mounting 14 5 cm 14 5 cm 140 145 cm 115 125 cm 2 3 4 5 1 ALTO UP HAUT OBEN 1 2 2 3 43...
Страница 45: ...Minitouch mounting 150 cm 120 cm 45...
Страница 76: ...Load management module 76...
Страница 78: ...78...
Страница 107: ...107...
Страница 108: ...7 edizione 03 2014 cod 2G40001063...