InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
72
G05
Generator Short Circuit Shutdown
Units:
percentage [%]
Step:
Range:
100
– 500 %
Default value:
150 %
Delay:
Generator Short Circuit
shutdown occurs when generator current exceed preset current limit longer
G06
Generator Short Circuit Delay
Units:
seconds [s]
Step:
0,01 s
Range:
0
– 10,00 s
Default value:
0 s
s
Delay:
Delay for the
Generator Short Circuit
alarm. The limit for this alarm is adjustable by setpoint
Generator Short Circuit Shutdown