B09 Nominal Current
Units:
Ampere [A]
Step:
1 A
Range:
1
– 1000 A
Default value:
50 A
It is nominal generator current. This value is used as a base for
(shutdown). For overcurrent limit set the setpoint
Generator Short Circuit Shutdown
Nominal Current can be different from generator rated current value.
B10 CT Ratio
Units:
Ampere [A]
Step:
A / 5 A
Range:
1
– 5000 A
Default value:
50 A
Gen-set phases current transformers ratio.
For CT Ratio < 50 the values of power and current are displayed in a controller with one decimal.
For CT Ratio
≥ 50 the values of power and current are displayed in a controller with integral numbers.
B11 Nominal RPM
Units:
RPM
Step:
1
Range:
100-4000
Default value:
1500
Nominal engine speed.