InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
52
I23
Oil Pressure Analog
Analog input for oil pressure measurement. When the measured value exceeds the preset threshold
the red LED above
Stop
button will blink, the
general shutdown symbol will be displayed on LCD’s
upper right corner, the oil pressure symbol will be displayed on event log with running hours stamp
and the shutdown procedure will occur. For more details see
procedure in chapter
Alarm, Events and History Management.
Default threshold is 1 Bar of measurement range. You can choice one from five default resistive
sensors (VDO, Datcon) or you can create your own sensor curve.
You can setup shutdown threshold (
in Engine parameters and
protection group.
N
OTE
:
Input has 3s delay.
VDO 5 Bar
Ohm
Bar
1
10
0
2
50
1
3
85
2
4
119
3
5
152
4
6
180
5