O08 Prestart
The output is activated while engine is cranking, but prior to the engine start. It is deactivated when
25% of Nominal RPM speed is reached. This output is typically used for pre-heat or pre-lubrication.
Prestart Time
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Cranging Fail
Pause 8 s
Gen-set start failed
On
Off
Starter Output
Time
Start
Prestart Output
On
Prestart Time
Maximum
Cranking Time
0 - 60 s
Gen-set start failed – shutdown,
if the voltage or frequency are not in
the limit
On
Off
Time
Start
Engine run
Max. Stab. Time 7 s
Min. Stab. Time
Starter Output
Prestart Output
On
O09 ECU Power Relay
This output is to be used for "keyswitch" input to the ECU. If the particular ECU does not have
keyswitch or similar input, it can be used for control of DC power for the ECU.
The output closes together with
and remains closed while the engine is running. It is
opened when a stop command is received. (I.e. together with the
).
N
OTE
:
The controller does not evaluate the communication failure alarm during the period when this output
is not active.
Содержание InteliNano NT Plus
Страница 36: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 36 Figure 8 1 BINARY OUTPUT SETTING EXAMPLE ...
Страница 45: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 45 Figure 9 1 BINARY INPUT SETTING EXAMPLE ...
Страница 46: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 46 3x 3x Figure 9 2 ANALOG INPUT SETTING EXAMPLE ...
Страница 77: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 77 Figure 12 2 ...