InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
62
B04 Connection Type
Units:
Step:
Range:
1,2,3,4,5
Default value:
4
Generator winding connection.
Setpoint code
Value
Meaning
B04
1
Mono Phase
B04
2
Split Phase
B04
3
3Ph3Wire
B04
4
3Ph4Wire
B04
5
Autodetect
Mono Phase: MONOPHASE,
Single-phase measurement
– 1PH
Split Phase:
DOUBLE DELTA Connection, Split Phase,
Single-phase measurement
– 1PH
3Ph3Wire:
DELTA Connection, 3 Phase without neutral - 3 Wires,
Three phas
e “delta” measurement – 3PD
3Ph4Wire:
STAR Connection, 3 phases and neutral - 4 wires,
Three phase “wye” measurement – 3PY
Autodetect:
High-Leg Delta
L1 >=100V; L1 <=140V
L2 >=140V
or
L3 >=100V; L3 <=140V
3Ph4Wire or 3Ph3Wire
L1 >=100V
L2 >=100V
or
L3 >=100V
Split Phase
L1 >=100V
L2 >=100V
or
L3 <= 20V
Mono Phase
L1 >=100V
L2 <= 20V
or
L3 <= 20V
shutdown
N
OTE
:
The Autodetect option is available only when
is disabled!
Содержание InteliNano NT Plus
Страница 36: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 36 Figure 8 1 BINARY OUTPUT SETTING EXAMPLE ...
Страница 45: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 45 Figure 9 1 BINARY INPUT SETTING EXAMPLE ...
Страница 46: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 46 3x 3x Figure 9 2 ANALOG INPUT SETTING EXAMPLE ...
Страница 77: ...InteliNano NT Plus SW version 2 0 1 x ComAp July 2015 77 Figure 12 2 ...