![ComAp InteliNano NT Plus Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/comap/intelinano-nt-plus/intelinano-nt-plus_reference-manual_2638959057.webp)
InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
57
Datcon
Low °C
Ohm
°C
1
6
150
2
8
140
3
11
130
4
15
120
5
21
110
6
30
100
7
43
90
8
63
80
9
95
70
10
113
66
11
146
60
12
229
50
13
372
40
14
624
30
15
819
25
16
1014
20
17
1209
15
18
1404
10
19
1599
5
20
1794
0
21
1989
-5
I29
Fuel Level SD
When this binary input is activated the red LED above
Stop
button will blink, the general warning
symbol will be displayed on LCD’s upper right corner. Fuel Level SD symbol will be displayed on event
log with running hours stamp and shutdown procedure will occur.
Input has 10s delay.