InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
91
Default:
0
7.6.9 Load Integral
[%]
This setpoint is giving Load limit integration factor.
Step:
0.1
Range:
0.0% - +100.0%
Default:
0
7.6.10 Load CMP Input
[RPM, ECU:Load, CU:AI1, CU:AI2, CU:AI3,
CU:AI4, CU:AI5, CU:AI6, CU:AI7, CU:AI8,
CU:AI9, AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4]
This setpoint is for Load limit comparetor with hysteresis analog input selection. Source can be
adjusted from controller RPM pick-up, ECU, analog inputs or from extension module inputs.
Default state:
RPM
7.6.11 Load CMP Off
Limit to close LBO LoadSwitch
Step:
1
Range:
-10000 - +10000
Default:
95
7.6.12 Load CMP On
Limit to open LBO LoadSwitch
Step:
1
Range:
-10000 - +10000
Default:
90
7.7 Engine protect
7.7.1 Eng prot del
[s]
During the start of the engine, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the
Protection del
time. The time starts after reaching
Start RPM
.
Step:
1s
Range:
0 - 300s
Default:
5s