InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
97
7.7.24 AIN4 Eval
[NORMAL, CLASS C]
NORMAL:
Protection behaves according to the standard configuration of Wrn/Sd alarm in
LiteEdit AINx configuration screen. Default state.
CLASS C:
The protection is
type “Running only” and does not depend on Running only tick in
LiteEdit AINx Alarm properties configuration window. Protection (Class C) is working
after AINx Del or sooner when appropriate value increases over AINx Wrn limit +3
seconds - after engine start. Warning/ShutdDown protection is activated with fix delay
0,5s.
H
INT
Class C protection is working and corresponding setpoints are visible only when corresponding AIN is
configured in Modify->Alarm properties-> Direction-> Window prot.
7.7.25 AIN4 LowWrn
[ ]
Low Warning limit level for AIN4
Step:
1
Range:
0 - 10000
Default:
20
7.7.26 AIN4 LowSd
[ ]
Low ShutDown limit level for AIN4
Step:
1
Range:
0 - 10000
Default:
10
7.7.27 AIN4 LowDel
[s]
Low level protection delay for Wrn and Sd of AIN4
Step:
1s
Range:
0 - 3600s
Default:
10s
7.7.28 AIN4 HighWrn
[ ]
High Warning limit level for AIN4
Step:
1
Range:
0 - 10000
Default:
20
7.7.29 AIN4 HighSd
[ ]
High ShutDown limit level for AIN4
Step:
1
Range:
0 - 10000
Default:
10