10 Binary output functions
H
INT
Any Binary input can be configured to any InteliDrive Lite controller terminal or changed to different
function by LiteEdit PC tool. There is adjustable delay when any binary input is configured as
protection.
10.1 Binary outputs InteliDrive Lite - default
BO1
Starter
BO2
Fuel solenoid
BO3
Prestart
BO4
Alarm
BO5
Horn
BO6
Not used
BO7
Not used
10.2 Binary outputs
– list
Configuration of binary outputs is feasible easily by combo box menu in the configuration window
Modify.
10.2.1 Not used
Output has no function.
10.2.2 Starter
Closed relay energizes the starter of engine.
The relay opens if:
the strating speed is reached or
maximum time of cranking is exceeded or
request to stop comes up
10.2.3 Fuel solenoid
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
Emergency stop comes or
cooled engine is stopped or
in pause between repeated starts