InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
87
7.5.4 Request 1
[-]
Regulator requested value.
Step:
1
Range:
-10000 - +10000
Default:
0
7.5.5 Request 2
[-]
Regulator requested value when LBI Request2 is active.
Step:
1
Range:
-10000 - +10000
Default:
0
7.5.6 Reg Gain
[%]
This setpoint is giving regulator gain factor. See Hint below.
Step:
0.1%
Range:
-200.0 - +200.0%
Default:
10%
7.5.7 Reg Integral
[%]
This setpoint is giving regulator integration factor. See Hint below.
Step:
0.1
Range:
0.0% - +100.0%
Default:
10%
H
INT
InteliDrive Lite controllers include PI loop for speed or analog output regulation. The requested value
is given by setpoints Request 1, 2. This loop is working like Proportional-Integral regulation with
setpoints Reg Gain and Reg Integral for each part and these parts affect each other.
The controller output is given by:
Reg Gain * e(t) + Reg Integral * ʃ e(t) dt,
where e(t) is deviation of actual value e(t) = Request 1, 2
– Measured value.