InteliDrive Lite - 1.2.1 Global guide
67
Timer2
Output activates when Timer2 is active. Simultaneously the engine is started when is in AUT mode.
Glow plugs
The output closes prior to the engine start (Prestart) and opens when Starting RPM speed is reached. During
repeated crank attempts the output is opened.
LBO Glow Plugs is closed prior to every attempt to start the engine for time set in setpoint Preglow.
Conveyor
Binary output function of Conveyor. See Binary input Conveyor.
SpeedSwitch
Binary output from Speed switch comparator – see Regulator setpoint group.
LoadSwitch
Binary output from Load switch comparator – see Load limit setpoint group.
Close Load
Output is controlled by panel 0/1 button when Basic settings: Panel Button = Close Load, engine is running and
no Sd/Cd alarm is active. Close Load output is not closed in Idle and Cooling states and is disconnected when
any Sd/Cd alarm is activated.
Toggle
Output is controlled by panel 0/1 button when Basic settings: Panel Button = Toggle. This setting changes the
Toggle output without any relation to Engine state or Alarm activity even if in OFF mode.
RemoteControl 1, 2, 3, 4, 5, 6, 7, 8
Allows configure Remote control switches to physical binary outputs. These switches are accessible from PC
tools LiteEdit (see picture below) or InteliMonitor by button
and it can be controlled via ModBus
communication.
SpdUpButtEcho
Output copies level of button Speed Up which is useful for manual speed settings of mechanical engines
directly from controller.