InteliDrive Lite - 1.2.1 Global guide
164
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 10000 [s]
Default value
10 s
Force value
Step
1 s
Comm object
13367
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Low level protection delay for Wrn and Sd of AIN4
Setpoint name depends on setting of AIN4 (maximum length is 14 characters).
AIN4 LowDel
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 10000 [U16]
Default value
20 U16
Force value
Step
1 U16
Comm object
13368
Related applications
Config level
Standard
Setpoint visibility
Always
Description
High Warning limit level for AIN4
Setpoint name depends on setting of AIN4 (maximum length is 14 characters).
AIN4 HighWrn
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 10000 [U16]
Default value
10 U16
Force value
Step
1 U16
Comm object
13369
Related applications
Config level
Standard
Setpoint visibility
Always
Description
High ShutDown limit level for AIN4
Setpoint name depends on setting of AIN4 (maximum length is 14 characters).
AIN4 HighSd