InteliATS
NT
PWR, SW version 1.0, ©ComAp – March 2009
45
IA-NT- PWR-1.0-Reference Guide R1.pdf
Time
[HHMMSS]
Real time clock adjustment.
Date
[DDMMYYYY]
Actual date adjustment.
Timer 1..2 Repeat
[NONE/MONDAY/TUESDAY/WEDNESDAY/THURSDAY/WEDNESDAY/FRI
DAY/SATURDAY/SUNDAY/MON-FRI/MON-SAT/MON-SUN/SAT-SUN]
Defines TIMER 1 activation. Binary output TIMER 1 is internally linked with Rem Start/Stop binary
input. Refer to binary inputs for details.
NONE:
Timer function is disabled
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:
Timer is activated on daily basis.
MON-FRI,
MON-SAT,
SAT-SUN:
Timer is activated on selected day interval.
Timer1..2 ON Time
Day time when Timer output activates.
Timer1..2Duration
Duration of Timer output is active.
Step:
1 min
Range:
1 – 1440 s
SMS/E-Mail
Remote alarm messaging
If a GSM modem and/or Internet Bridge is connected to the controller, the controller can send SMS
messages and/or emails in the moment when a new alarm appears in the Alarm list. The message will
contain a copy of the Alarm list.
To enable this function, you should select with setpoints Yel Alarm Msg and Red Alarm Msg, which
levels of alarms shall be announced (red/yellow/both) and also enter valid GSM phone number and/or
e-mail address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is possible to put either a
GSM number or e-mail to both setpoints.
N
OTE
:
An internet module must be available for sending of e-mails. Similarly, a GSM modem is necessary for
sending of SMS.
N
OTE
:
There are 5 attempts for any active call (SMS/E-Mail). Timeout for connection is 90 sec and after 120
sec controller starts the next attempt. During the time the IA-NT is trying to send an active call type,
incoming calls are blocked.
Yel Alarm Msg
[DISABLED, ENABLED]
Set this setpoint to YES if you want to get messages when a
yellow
(warning) alarm occurs.