InteliATS
NT
PWR, SW version 1.0, ©ComAp – March 2009
52
IA-NT- PWR-1.0-Reference Guide R1.pdf
Alarm Management
Following alarms are available:
•
Warning
•
Trip
•
Mains
failure
Warning (WRN)
When warning comes up, only alarm outputs and common warning output are closed.
Possible warnings:
See
List of possible events
Trip (TRP)
When the trip alarm comes up, InteliATS
NT
opens outputs GCB CLOSE/OPEN, GENSTART/STOP
and PRESTART to stop the engine immediately. Alarm outputs and common shutdown output are
closed. Active or not reset protection disables start.
Possible shut-down alarms:
See
List of possible events
Mains failure (MF)
Mains failure detection depends on
Auto mains failure (AMF)
setpoints (levels and delays) adjusting.
When the mains failure comes up, mains circuit breaker is opened.
Possible mains failure reasons:
See
List of possible events
N
OTE
:
Mains failure is not written to alarm list!