16
General Operating specifications
System Voltage
C440-HVAD Diversion Controller
12V
24V
48V
Minimum operating voltage
10.5v
10.5v
10.5v
Maximum allowable intermittent/surge voltage (1)
100v
100v
100v
Maximum input from solar panels (VOC)
24v
48v
96v
Preferred maximum input from solar
panels
21v
42v
84v
Maximum continuous solar charge amperage
125A
125A
125A
Maximum continuous diversion amperage
150A
150A
150A
Maximum surge solar charge amperage
440A
440A
440A
Maximum surge diversion amperage
(resistive) – Longer surges will be
restricted by the installed breakers.
440A
440A
440A
Energy consumed by the electronics (meters off, solenoid
off - standby current)
< .1W
< .15W < .3W
Energy consumed by the electronics (meters on, solenoid
on)
< 1A
< .75A
< .5A
Minimum float setting (volts)
12.0
24
48
Maximum float setting (volts)
24
48
96
Factory default float setting (volts)
13.5
27
54
Minimum bulk setting (volts)
12
24
48
Maximum bulk setting (volts)
24
48
96
Factory default bulk setting (volts)
14.4
28.8
57.6
Time in absorption charge once bulk set point has been reached.
2 hours
2 hours 2 hours
Time in equalize charge once equalize set point has been reached. 2 hours
2 hours 2 hours
(1) -- Voltages spikes above 100v at the input terminal will trigger the over-voltage
protection circuitry causing the isolation circuit to be engaged.
The red over voltage LED will be
lighted (on the small PCB board in the center of the unit). The controller must be un-powered for
at least 10 seconds to clear this condition.