background image

 

15

Extended Diversion Mode -- EDM 

 

The basic operating philosophy of a diversion controller is quite simple. Monitor the battery voltage, and if it should 
rise to a predetermined level, connect a diversion load of sufficient size, to the battery or energy source to prevent the 
battery voltage from increasing any further.  The amount of time the diversion load is connected is generally only 2 to 
30 seconds. In this amount of time, the battery voltage will have dropped enough to be back in the normal region. The 
controller will continue to engage and disengage the solenoid as often as necessary to prevent battery overcharge. This 
is the normal mode of operation. The microprocessor uses several advanced algorithms to prevent rapid relay cycle, 
yet it is common for the solenoid to be engaged and disengaged a few times per minute. This constant attention keeps 
the batteries very close to (or just below) the trip point you have set. 

There are however, situations where you would really like the controller to engage the solenoid for a longer period of 
time once the batteries get to a “full” state. This is what we call the Extended Diversion Mode. On the HVA and 
previous analog controllers, the EDM mode was selected via a jumper.  On the HVAD, which is fully digitally 
configured, the EDM “mode” (to continue with the HVA legacy) can be configured much more specifically via the 
user menu options (advanced menu).  Via this menu option, you can set both the minimum time the relay should stay 
engaged as well as how low the batteries will be allowed to drop (percentage based). Once the batteries reach the 
upper trip point you have set (the same trip point as the non EDM mode), the controller will engage and disengage the 
solenoid based on these advanced parameters.   See the menu system in this manual for more information on how to 
configure these settings. 

The EDM mode is very useful for running such items as water pumps, small grid tie inverters, or even alt-currency 
mining that you do not want turning on and off every few seconds. When you configure the EDM mode, the wiring 
remains the same; the difference is that the load you connect will be engaged for a longer period of time. 

It is very important that the load you choose is 100% dependable if this controller is being used to prevent battery 
overcharge. If the load is not present, then your batteries will overcharge. Grid-tied inverters will not provide a load ti 
to the controller if the grid fails (power outage due to thunderstorm etc.). Such a loss of load can also cause damage to 
your wind turbine if it depends on this load.  

If you will be using the EDM mode with a load that may not be present at all times, then it is important that you have 
another controller in parallel that is also monitoring the system with a slightly higher trip point. This second, failsafe 
controller will then divert the excess energy to a diversion load that is 100% dependable should the 1

st

 controller’s 

load not be present or capable of disbursing all of the excess energy. 

As in the case with the normal mode, the load you connect cannot exceed the capacity of the solenoid. Do not attempt 
to hookup highly inductive loads, as the solenoid will be damaged due to high currents during the motor start. 

Содержание C440-HVAD

Страница 1: ...e managed through the user interface Relay on time can be controlled and set for diversion times up to several hours Upper and lower set points can both be set Automatic LCD back light dimming to save...

Страница 2: ...ies to complete a full charge of the batteries The internal LED on the upper left of the large PCB board motherboard is lighted when the solenoid is engaged The red LED on the small daughter board is...

Страница 3: ...3...

Страница 4: ...select the current value and then press the up button to exit the menu For example To change the float set point of the controller Press the Enter Up Down or Scroll button on the front panel The Charg...

Страница 5: ...mechanical controller that does have the ability to track multiple voltages and react accordingly Additional charging logic has also been added including such features as re bulking an absorb mode th...

Страница 6: ...solid state controller and may allow the voltage to rise or fall further than optimal To alleviate this condition it is recommended that your charge source s not exceed the battery bank s amp hour ca...

Страница 7: ...state of the solenoid of less than two seconds Given these settings the controller may turn on and off the solenoid several times per minute This is great if you want to keep the batteries as close to...

Страница 8: ...n it is connected to the batteries The solar VOC reading will only be accurate when the solenoid is enabled Hint Run the test cycle to watch how the enable disable of the solenoid affects the solar vo...

Страница 9: ...you may hear the solenoid s coil pull in as normal but see no difference in the solar amperage or solar voltage during the test This generally indicates the normally closed contacts of the solenoid ar...

Страница 10: ...the batteries along with the load the turbine remains more within its design realm always a good thing Please note this controller does not include a blocking diode or an A C to D C rectifier as thes...

Страница 11: ...designed specifically for 12 24 and 48 volt systems are by far a better choice A very acceptable diversion load is a power resistor These can be obtained via your Coleman Air dealer Various wattages a...

Страница 12: ...use the front panel buttons and display When mounting vertically the inputs of the controller should always be oriented downwards with the vent upwards to ensure the unit is able dissipate any captiv...

Страница 13: ...d the coil is active the solenoid s bottom contacts open and disconnect the electrical connection from the solar panels to your battery bank The wind hydro input is not switched disconnected and conne...

Страница 14: ...ircuits but they may be no competition to a direct lighting hit Many of our controllers have survived direct lighting hits due to the internal protective circuits yet the connected equipment like mete...

Страница 15: ...eries will be allowed to drop percentage based Once the batteries reach the upper trip point you have set the same trip point as the non EDM mode the controller will engage and disengage the solenoid...

Страница 16: ...tandby current 1W 15W 3W Energy consumed by the electronics meters on solenoid on 1A 75A 5A Minimum float setting volts 12 0 24 48 Maximum float setting volts 24 48 96 Factory default float setting vo...

Страница 17: ...witch can offer such a level of reliability For such systems our solid state controllers no relays or solenoids should be considered To replace the solenoid 1st ensure all power is removed from the un...

Страница 18: ...ms should be designed for no more than 125 amps continuous current Higher voltage higher amperage systems will result in a lower life expectancy of the solenoid We recommend our solid state controller...

Отзывы: