background image

 

8

the bulk set point you have entered, automatically calculates this depleted value set point to protect (as 
much as possible) the battery from an over-discharge. 

 
Please note: A lead-acid battery’s life is greatly reduced when the level of discharge is quite deep or the 
battery is allowed to enter into a “dead battery” state.   You should familiarize yourself with the parameters 
for your particular battery before setting these advanced parameters.  

 

 

4.  The View Submenu:  The view menu allows you to view the real time voltage and amperage of the connected 

solar and or turbine energy sources.  The controller incorporates two shunts, allowing it to measure both solar 
and turbine amperages simultaneously.  This feature is new to the HVAD, whereas previous controllers were 
only able to display the amperage for a single input.   

 

Note: If you do not utilize both wind and turbine inputs, it is possible (perhaps likely), that there will be a 
small amount of current that is displayed for the unused input.  For instance, if you are using only the solar 
input, the controller may sense a few tenths of an amp on the turbine input.  This is normal as there are stray 
currents in any system where large amperages are involved. 
 
Please note these very important electrical concepts:  When the solenoid is not enabled, the solar panels are 
effectively wired directly to the batteries through the normally closed contacts of the solenoid, just as if you 
had hooked the positive of the solar panel directly to the positive of the battery bank.  This means that the solar 
voltage and the battery voltage will be identical at that time.  The solar panels will move the voltage of the 
batteries up and the batteries will have moved the solar panel voltage down until they reach an equilibrium 
based on ohms law.  This means, the controller cannot report the VOC (voltage open circuit) of the solar panel 
input when it is connected to the batteries.  The solar VOC reading will only be accurate when the solenoid is 
enabled!  Hint: Run the test cycle to watch how the enable/disable of the solenoid affects the solar voltage. 
 
This same concept applies to the turbine input; however, the turbine input is never disconnected from the 
batteries, therefore the turbine voltage is always identical to the battery voltage and therefore it is not reported 
separately by the controller.  
 
Another concept to understand is that the solar voltage will always be the same as the battery (and turbine) 
voltage when you do not have an active solar input.  This seems impossible, yet due to the same fact that the 
solar input is tied to the battery positive via the normally closed contacts of the solenoid, the controller will 
“see” the battery voltage on the solar input, with no way to determine if it is battery voltage or solar voltage. 
 
When the solenoid is enabled, the solar voltage will be “floating” (it is not connected to anything) without an 
active input and may not be considered accurate at that time, as there can be stray inductances present.  
Essentially, if you do not have any solar hooked up, then just ignore any voltage readings the controller may 
display for the solar input. 
 
The current reading (amperage) of the solar and turbine inputs will be zero (or very close to zero), if there is no 
active input for that source.  When the solenoid is enabled, the solar current will drop to zero. When the 
solenoid is not enabled, the solar input will be at its maximum.   Both turbine and solar amperage readings 
should always be accurate within a few percent, regardless of the active inputs (solar only, turbine only, or 
both active).  Voltages can be misleading due to the concepts discussed above, so using amperages is the key 
to determining the performance of the inputs.  

 
Other Menus and Submenus:   
 
In addition to changing the charging parameters, the menu system can be used to view the maximum voltages and 
amperages reached during the active charge cycle.  These values are reset each time the charge mode is changed (a 

Содержание C440-HVAD

Страница 1: ...e managed through the user interface Relay on time can be controlled and set for diversion times up to several hours Upper and lower set points can both be set Automatic LCD back light dimming to save...

Страница 2: ...ies to complete a full charge of the batteries The internal LED on the upper left of the large PCB board motherboard is lighted when the solenoid is engaged The red LED on the small daughter board is...

Страница 3: ...3...

Страница 4: ...select the current value and then press the up button to exit the menu For example To change the float set point of the controller Press the Enter Up Down or Scroll button on the front panel The Charg...

Страница 5: ...mechanical controller that does have the ability to track multiple voltages and react accordingly Additional charging logic has also been added including such features as re bulking an absorb mode th...

Страница 6: ...solid state controller and may allow the voltage to rise or fall further than optimal To alleviate this condition it is recommended that your charge source s not exceed the battery bank s amp hour ca...

Страница 7: ...state of the solenoid of less than two seconds Given these settings the controller may turn on and off the solenoid several times per minute This is great if you want to keep the batteries as close to...

Страница 8: ...n it is connected to the batteries The solar VOC reading will only be accurate when the solenoid is enabled Hint Run the test cycle to watch how the enable disable of the solenoid affects the solar vo...

Страница 9: ...you may hear the solenoid s coil pull in as normal but see no difference in the solar amperage or solar voltage during the test This generally indicates the normally closed contacts of the solenoid ar...

Страница 10: ...the batteries along with the load the turbine remains more within its design realm always a good thing Please note this controller does not include a blocking diode or an A C to D C rectifier as thes...

Страница 11: ...designed specifically for 12 24 and 48 volt systems are by far a better choice A very acceptable diversion load is a power resistor These can be obtained via your Coleman Air dealer Various wattages a...

Страница 12: ...use the front panel buttons and display When mounting vertically the inputs of the controller should always be oriented downwards with the vent upwards to ensure the unit is able dissipate any captiv...

Страница 13: ...d the coil is active the solenoid s bottom contacts open and disconnect the electrical connection from the solar panels to your battery bank The wind hydro input is not switched disconnected and conne...

Страница 14: ...ircuits but they may be no competition to a direct lighting hit Many of our controllers have survived direct lighting hits due to the internal protective circuits yet the connected equipment like mete...

Страница 15: ...eries will be allowed to drop percentage based Once the batteries reach the upper trip point you have set the same trip point as the non EDM mode the controller will engage and disengage the solenoid...

Страница 16: ...tandby current 1W 15W 3W Energy consumed by the electronics meters on solenoid on 1A 75A 5A Minimum float setting volts 12 0 24 48 Maximum float setting volts 24 48 96 Factory default float setting vo...

Страница 17: ...witch can offer such a level of reliability For such systems our solid state controllers no relays or solenoids should be considered To replace the solenoid 1st ensure all power is removed from the un...

Страница 18: ...ms should be designed for no more than 125 amps continuous current Higher voltage higher amperage systems will result in a lower life expectancy of the solenoid We recommend our solid state controller...

Отзывы: