background image

 

17

 

 

 

 

 

 

 

 

For indoor use only. Install in a non-corrosive, dry environment only.

 

 

 

 

External dimensions of the enclosure (Inches)  8.5 x 12.5 x 4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum ambient air temperature 

-20F

 

 

 

 

 

 

*2) Maximum ambient air temperature 
(150 Amps) 

85F

 

 

 

 

 

 

*2) Maximum ambient air temperature 
(100 Amps) 

110F

 

 

 

 

 

 

Maximum ambient air temperature  
(60Amps) 

140F

 

 

 

 

 

 

 

 

 

 

 

 

 

Operations above or below the maximum temperature range may result in loss of accuracy and/or 
a reduction in current handling capability

 

 

 

 

 

 

 

 

 

Designed for battery-based systems only.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These specifications and measurements are subject to periodic change without notice.

 

 

Replacing the Solenoid: 
 

The solenoid is a mechanical switch that has a limited life expectancy that is dependent on many factors including, but 
not limited to, the number of times it has cycled, the amount of amperage it must carry and switch, the voltage across 
the terminals as well as ambient heat in the installation environment.  In active systems, the solenoid will eventually 
need to be replaced.  Although we use only the highest quality silver contact solenoids available that support both 
continuous and surge amperages that far exceed the design of this controller, it is a mechanical device that is subject to 
failure.  The higher the voltage and amperage of your system, the shorter the life expectancy of this solenoid is likely 
to be.  This controller should not be considered for use in solar systems where absolute reliability is required.  No 
mechanical switch can offer such a level of reliability. For such systems, our solid-state controllers (no relays or 
solenoids) should be considered. 

 

To replace the solenoid, 1

st 

ensure all power is removed from the unit.  2

nd

, disconnect all of the wires and straps 

that are tied to or bolted on to the solenoid. 3

rd

, using a Phillips head screwdriver, remove the two #10 screws that 

fasten the solenoid to the back-plate.  The HVAD uses Zimmerman nuts that will not fall out or turn as you remove 
the screws.  Once the solenoid is free, simply lift it out and replace it by reversing this procedure.  Take special care 
not to over-tighten the nuts on the terminals of the solenoid as they can be stripped and cross-threaded very easily.: 

Automatic Nominal Battery Bank detection: 

When power is first applied to the HVAD controller, the voltage of the connected battery bank is measured to 
determine if the controller should operate in the 12, 24 or 48-volt mode.  This process is automatic and eliminates the 
need for manual jumper settings or other user intervention.  This process; can however, report the wrong value to the 
controller if the connected battery bank has been depleted beyond normal limits (A fully dead battery). For example, if 
a 24-volt battery has been allowed to deplete to perhaps 15 volts and the controller is restarted during this period, then 
the controller will assume it is connected to a 12-volt bank, not 24 volt.  If this occurs, then simply increase the bulk 
charge point and let the battery bank recharge. Once the battery is recharged within normal limits; use the menu 
system to reset the factory defaults or simply restart your controller. 

Содержание C440-HVAD

Страница 1: ...e managed through the user interface Relay on time can be controlled and set for diversion times up to several hours Upper and lower set points can both be set Automatic LCD back light dimming to save...

Страница 2: ...ies to complete a full charge of the batteries The internal LED on the upper left of the large PCB board motherboard is lighted when the solenoid is engaged The red LED on the small daughter board is...

Страница 3: ...3...

Страница 4: ...select the current value and then press the up button to exit the menu For example To change the float set point of the controller Press the Enter Up Down or Scroll button on the front panel The Charg...

Страница 5: ...mechanical controller that does have the ability to track multiple voltages and react accordingly Additional charging logic has also been added including such features as re bulking an absorb mode th...

Страница 6: ...solid state controller and may allow the voltage to rise or fall further than optimal To alleviate this condition it is recommended that your charge source s not exceed the battery bank s amp hour ca...

Страница 7: ...state of the solenoid of less than two seconds Given these settings the controller may turn on and off the solenoid several times per minute This is great if you want to keep the batteries as close to...

Страница 8: ...n it is connected to the batteries The solar VOC reading will only be accurate when the solenoid is enabled Hint Run the test cycle to watch how the enable disable of the solenoid affects the solar vo...

Страница 9: ...you may hear the solenoid s coil pull in as normal but see no difference in the solar amperage or solar voltage during the test This generally indicates the normally closed contacts of the solenoid ar...

Страница 10: ...the batteries along with the load the turbine remains more within its design realm always a good thing Please note this controller does not include a blocking diode or an A C to D C rectifier as thes...

Страница 11: ...designed specifically for 12 24 and 48 volt systems are by far a better choice A very acceptable diversion load is a power resistor These can be obtained via your Coleman Air dealer Various wattages a...

Страница 12: ...use the front panel buttons and display When mounting vertically the inputs of the controller should always be oriented downwards with the vent upwards to ensure the unit is able dissipate any captiv...

Страница 13: ...d the coil is active the solenoid s bottom contacts open and disconnect the electrical connection from the solar panels to your battery bank The wind hydro input is not switched disconnected and conne...

Страница 14: ...ircuits but they may be no competition to a direct lighting hit Many of our controllers have survived direct lighting hits due to the internal protective circuits yet the connected equipment like mete...

Страница 15: ...eries will be allowed to drop percentage based Once the batteries reach the upper trip point you have set the same trip point as the non EDM mode the controller will engage and disengage the solenoid...

Страница 16: ...tandby current 1W 15W 3W Energy consumed by the electronics meters on solenoid on 1A 75A 5A Minimum float setting volts 12 0 24 48 Maximum float setting volts 24 48 96 Factory default float setting vo...

Страница 17: ...witch can offer such a level of reliability For such systems our solid state controllers no relays or solenoids should be considered To replace the solenoid 1st ensure all power is removed from the un...

Страница 18: ...ms should be designed for no more than 125 amps continuous current Higher voltage higher amperage systems will result in a lower life expectancy of the solenoid We recommend our solid state controller...

Отзывы: