background image

 

7

absorb mode is considered adequate, the timer will be decremented by one minute.  If on the other hand, the 
performance is below the standard, the timer will not be decremented, which can result in a charge cycle that 
lasts much longer to ensure the batteries actually receive the best charge possible in less than optimal charging 
conditions.   
 
The green LED on the front cover will be lighted when the processor determines the performance is 
high
 and off when the performance is not high enough to properly charge the batteries.  This allows you to 
quickly visualize the real time charging performance that the controller is detecting. Often the green LED will 
blink on and off randomly and rapidly as the solar/wind energy fluctuates.  
 

2.  Turning on or off the Equalize mode.  By default, the equalize mode is not enabled.  To start a manual 

equalize, select the Equalize submenu, scroll right or left to the “Start Equalize?”. When this submenu is 
displayed, press the “Up/Down” button to select “YES” and then press the “Enter” button to request this mode.  
The equalize mode will then be queued.  The controller will not actually start the equalize mode until the bulk 
set point has been reached. Once the mode is started, the countdown timer will start and the mode will stay in 
affect until the timer expires. The length of time in this mode is controlled by the “Equalize Minutes” submenu 
option.  The equalize mode is not performance based and will not be restarted automatically due to low current 
conditions.  
 
The automatic equalize: 
Changing the Equalize days from “0” to any number up to 90 will enable this 
feature.  The equalize function will then run once the day timer has been triggered and the bulk set point has 
been achieved.  The equalize will not actually start if the bulk set point is not achievable via the solar/turbine 
charge inputs.   
 

3.  The Advanced Menu.  The factory settings for the HVAD are to engage and disengage the solenoid as soon 

as the currently active set point (bulk, float, equalize), is reached and to allow the battery voltage to drop by no 
more than 6% from that setting.  In addition, the microprocessor will attempt to track these set points as much 
as possible but will not allow an enabled state of the solenoid of less than two seconds.  Given these settings, 
the controller may turn on and off the solenoid several times per minute.  This is great if you want to keep the 
batteries as close to the set point as possible, but not suitable if the primary purpose of the controller is to run a 
pump, grid tied inverter, perhaps even Bitcoin mining equipment or any other real world load that needs to be 
engaged for a longer period of time in order to be useful.  This is where the advanced menu is used.   

 

a)  The relay offset setting:  This setting allows you to specifically set the “lower set point” for any mode 

based on a percentage of the upper set point.  For example.  The factory setting for this value is 6% and 
the factory set point for the bulk mode in a 12-volt system is 14.4 volts.  Given these two values, the 
upper set point will be 14.4 volts and the lower set point will be a drop of 6% (or 94% of the upper set 
point), yielding a lower set point of 13.4 volts.  This means that the solenoid will be enabled when the 
battery voltage rises to 14.4 volts and disabled when the battery bank drops to 13.4 volts.  These upper 
and lower voltages will cycle back and forth as the solenoid is engaged and disengaged; providing 
there is adequate charge current to raise the battery voltage to the upper trip point.  This distance 
between the upper and lower trip point is called hysteresis and is necessary in a solenoid-based 
controller.  The hys-ter-e-sis width can be narrowed (the lower set point is brought upwards) by 
lowering the relay-offset percentage. In the same manner, a higher percentage will yield a lower low 
set point.  The lower the set point, the longer the solenoid will stay engaged waiting for the battery to 
drop.  This setting alone can often be used to control a pump or similar device, where you desire to run 
the load as long as the batteries are not depleted past a certain point. 

b)  The Minimum relay on time. This 2

nd

 advanced solenoid parameter allows setting a minimum enable 

time of the solenoid from 2 seconds up to many minutes.  This setting can therefore allow a particular 
load to be turned on for a minimum of, for example, 10 minutes, without regard to the lower set point.  
During this time, the microprocessor still monitors the battery bank and will exit this timer if the 
battery drops considerably and is considered by the controller to be depleted.  The processor, based on 

Содержание C440-HVAD

Страница 1: ...e managed through the user interface Relay on time can be controlled and set for diversion times up to several hours Upper and lower set points can both be set Automatic LCD back light dimming to save...

Страница 2: ...ies to complete a full charge of the batteries The internal LED on the upper left of the large PCB board motherboard is lighted when the solenoid is engaged The red LED on the small daughter board is...

Страница 3: ...3...

Страница 4: ...select the current value and then press the up button to exit the menu For example To change the float set point of the controller Press the Enter Up Down or Scroll button on the front panel The Charg...

Страница 5: ...mechanical controller that does have the ability to track multiple voltages and react accordingly Additional charging logic has also been added including such features as re bulking an absorb mode th...

Страница 6: ...solid state controller and may allow the voltage to rise or fall further than optimal To alleviate this condition it is recommended that your charge source s not exceed the battery bank s amp hour ca...

Страница 7: ...state of the solenoid of less than two seconds Given these settings the controller may turn on and off the solenoid several times per minute This is great if you want to keep the batteries as close to...

Страница 8: ...n it is connected to the batteries The solar VOC reading will only be accurate when the solenoid is enabled Hint Run the test cycle to watch how the enable disable of the solenoid affects the solar vo...

Страница 9: ...you may hear the solenoid s coil pull in as normal but see no difference in the solar amperage or solar voltage during the test This generally indicates the normally closed contacts of the solenoid ar...

Страница 10: ...the batteries along with the load the turbine remains more within its design realm always a good thing Please note this controller does not include a blocking diode or an A C to D C rectifier as thes...

Страница 11: ...designed specifically for 12 24 and 48 volt systems are by far a better choice A very acceptable diversion load is a power resistor These can be obtained via your Coleman Air dealer Various wattages a...

Страница 12: ...use the front panel buttons and display When mounting vertically the inputs of the controller should always be oriented downwards with the vent upwards to ensure the unit is able dissipate any captiv...

Страница 13: ...d the coil is active the solenoid s bottom contacts open and disconnect the electrical connection from the solar panels to your battery bank The wind hydro input is not switched disconnected and conne...

Страница 14: ...ircuits but they may be no competition to a direct lighting hit Many of our controllers have survived direct lighting hits due to the internal protective circuits yet the connected equipment like mete...

Страница 15: ...eries will be allowed to drop percentage based Once the batteries reach the upper trip point you have set the same trip point as the non EDM mode the controller will engage and disengage the solenoid...

Страница 16: ...tandby current 1W 15W 3W Energy consumed by the electronics meters on solenoid on 1A 75A 5A Minimum float setting volts 12 0 24 48 Maximum float setting volts 24 48 96 Factory default float setting vo...

Страница 17: ...witch can offer such a level of reliability For such systems our solid state controllers no relays or solenoids should be considered To replace the solenoid 1st ensure all power is removed from the un...

Страница 18: ...ms should be designed for no more than 125 amps continuous current Higher voltage higher amperage systems will result in a lower life expectancy of the solenoid We recommend our solid state controller...

Отзывы: