background image

b.

 

The temperature controller parameters must 

be setup for the lower leaving temperatures 

that the system will generate. 

c.

 

Also, some temperature thermostats may 

need to be adjusted. 

17.  

 

PUMP (DEPENDING ON DESIGN) 

a.

 

Systems with integral pump are typically 

setup to provide recirculating fluid for the 

chiller and some flow is routed for the process 

system.  Refer to the unit’s actual design for 

details. 

b.

 

A secondary pump may be used for process 

specific applications, referred to as Process 

Pump. 

18.  

 

TANK (DEPENDING ON DESIGN) 

a.

 

Systems with integral tank will typically be 

304 Stainless Steel with Open Top with 

Shoebox Type Lid, Fluid Level Sight glass, Fill 

Port, & Drain Plug. 

19.  

 

HEAT EXCHANGER (DEPENDING ON DESIGN) 

a.

 

A heat exchanger is used to transfer heat 

typically from the chiller fluid circuit to a 

separate process fluid circuit. 

20.  

 

REMOTE OPERATION/STATUS PANEL (OPTION) 

a.

 

Basic On/Off control switch with Cooling 

Mode status and Fault indicator light. 

21.  

 

REMOTE OPERATION CONTROLS (OPTION) 

a.

 

Various designs (contact Cold Shot Chillers for 

options) 

22.  

 

SWITCHOVER SYSTEM (CHILLER BYPASS) 

(

OPTIONS

a.

 

Manual City Switchover (MCSO) (Option) 

a)

 

System valves which can be aligned to a 

backup water supply system such as the 

city water supply.  Outlet fluid flow is 

normally routed to the building’s drain 

system.  Valves are connected and must 

be actuated simultaneously or in the 

proper series to operate properly. 

 

Converting back is normally performed in 

the reverse order. 

b.

 

Automatic City Switchover (See ACSO 

literature) 

a)

 

System has electrically operated valves 

similar to MCSO, however it can be setup 

to change automatically based on a 

system safety situation. 

23.  

 

TANK LEVEL 

(OPTIONS)

 

a.

 

Float Valve 

a)

 

Located inside the tank, the float valve is 

a mechanically float-actuated valve 

supplied with a makeup water source of 

fluid for the tank. 

b)

 

The makeup water (such as city water 

supply) is connected to the pipe 

connection on the outside of the tank. 

c)

 

Water pressure, typically, must be less 

than 30psi. 

d)

 

When the level falls below a certain level, 

the valve will open and fill the tank.  

When it reaches the top setting 

adjustment, the valve closes. 

e)

 

If the valve does not maintain level: 

f)

 

Verify water pressure supply. 

g)

 

Verify the float adjustment. 

h)

 

Verify the mechanical linkages are free to 

move. 

i)

 

Verify there is no dirt or debris on the 

valve seat. 

b.

 

Tank Level Float Switch Solenoid Valve 

a)

 

Tank Level Switches 

b)

 

Float actuated switch(s)  mounted in the 

tank to monitor when tank is at different 

levels depending on design such as: 

a)

 

Safety  –  to stop the operation of 

something such as the chiller or 

pump. 

b)

 

Notification – to provide a signal for 

notification for manual refill or that 

another action must be performed. 

c)

 

Action  –  to provide signal for use 

with other system uses such as 

automatic fill systems. 

c)

 

Low Tank Level-  tank is at the low level 

point that will/should  begin filling the 

tank.  Above pump suction. 

d)

 

High Tank Level- level in tank is at or near 

top of tank  and tank filling will/should 

stop.  Tank may overflow. 

c.

 

Tank Level Float Controlled Solenoid Valve 

a)

 

A solenoid  valve  is  an electrically 

operated valve to start and stop fluid flow 

from an outside source of fluid such as 

city water to refill tank, typically. 

 

 

 

MNL_Standard-Basic_ACWC-24to240-E-(IN PROGRESS)_(0815).docx

- 12 -

 

 

Содержание ACWC-180-EM-DR-LT-0-5

Страница 1: ...Houston Texas 77032 Phone 800 473 9178 281 227 8400 Fax 800 473 9175 281 227 8404 www waterchillers com INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS ACWC 240 E model shown AIR COOLED WATER CHI...

Страница 2: ...ient fan control Casters optional d M20 Suitable for outdoor use to 20 F ambient Hot Gas Bypass and or Wind Baffles may be included Casters optional 7 Electrical Power See specification sheet Variatio...

Страница 3: ...has been inspected at the factory and released to the transportation agency without known damage Inspect carton s exterior for evidence of rough handling in shipment Carefully remove protective wrap...

Страница 4: ...unit to ensure proper oil return to compressors and fluid draining 2 When unit is in proper location secure unit to foundation or on vibration isolators as needed required by local requirements Fasten...

Страница 5: ...efrigerant Charge E ELECTRICAL POWER AND CONNECTIONS1 1 POWER SUPPLY Field wiring must comply with national and local codes a Install a branch circuit fused disconnect of adequate size to handle start...

Страница 6: ...ezing can occur from the external ambient or internal system temperatures 2 INTERNAL The evaporator or other heat exchanger is the primary component that is susceptible to freezing even during normal...

Страница 7: ...rating of the chiller 2 Some conditions are a Ambient conditions for air cooled systems b Condenser fluid for water cooled systems c Type of fluid being chilled d Design and setup of the chiller e Lea...

Страница 8: ...illed with fluid prior to starting e Systems with an open tank are typically capable of bleeding excess air that is returned to the tank when the system is operating Piping in and out are typically be...

Страница 9: ...LED readout which is an indication of the current temperature of the fluid in the chiller tank or Leaving Fluid Temperature depending on the specific chiller design 8 COOLING CYCLE Unit is now ready t...

Страница 10: ...F At this temperature an internal bi metal disk valve opens and causes the scroll elements to separate which stops compression Suction and discharge pressures balance while the motor continues to run...

Страница 11: ...SAFETY LPS a Monitors the pressure of the refrigerant suction line and will automatically open when the pressure drops below the set point and will automatically reset when pressure is above the non a...

Страница 12: ...ted valves similar to MCSO however it can be setup to change automatically based on a system safety situation 23 TANK LEVEL OPTIONS a Float Valve a Located inside the tank the float valve is a mechani...

Страница 13: ...with wire brush and or abrasive clothes and then the surface can be recoated to reduce future corrosion For severe environments use a durable epoxy paint that can create an oxygen barrier c Fasteners...

Страница 14: ...ecome jagged or splattered to avoid premature compressor and or pump failure Contactor points are consumable and their life is dependent on the amount of use and power characteristics at the unit 11 R...

Страница 15: ...t unless issue has been resolved Troubleshoot the switch DO NOT BYPASS IMPORTANT This condition can occur when the fluid in the evaporator nears freezing 9 Flow Switch Tripped switch open 9 Determine...

Страница 16: ...leak and recharge 4 Overcharged system 4 Remove refrigerant adjust charge FROSTED LIQUID LINE AFTER DRIER 1 Restricted filter drier 1 Remove restriction or replace COMPRESSOR WILL NOT LOAD UNLOAD HOT...

Страница 17: ...ply TEMPERATURE CONTROLLER ERROR 1 Temperature indication not accurate 1 Verify temperature sensor is in good condition and mounted properly Adjust the offset Typically it is only adjusted a few degre...

Страница 18: ...hnical Specification C Physical Installation Drawings D Electrical Drawings E Component Technical Pump options etc when available F Parts Warranty G Labor Warranty if included H Startup Checklist MNL_...

Страница 19: ...r starter or overload or the Tank Level is above the low level if included 2 Any issues with these items will result in a fault There is an initial delay bypassing the flow switch to permit flow to st...

Страница 20: ...switch is turned off or a fault occurs DISPLAYS Power ON typical Only at startup Normal display PV b190 DTB series Firmware V1 90 PV 51 3 Present Value SV r r Output type Relay and Relay SV 50 0 Set...

Страница 21: ...ow 9600 Leaving Fluid Temperature Too Low Freeze Thermostat is open 9700 Either 1 Pump Safety Circuit has tripped or 2 Low Tank Level at Start 9710 Either 1 Pump Safety circuit was tripped or 2 Low Ta...

Страница 22: ...d Rate 9600 LEN Communication Data Length 8 Prty Communication Parity Bit Even StoP Communication Stop Bit 1 Value Set Codes Code Description B ACTUAL SETTINGS r S Operation Mode rUn SP Decimal point...

Страница 23: ...PT LIFS 000 100 0 1 2730 Maximilian Drive Houston Texas 77032 Phone 800 473 9178 281 227 8400 Fax 800 473 9175 281 227 8404 www waterchillers com Liquid Flow Switch...

Страница 24: ...S Fan Cycling Pressure Switch FST Flow Safety Thermostat FZT Freeze Safety Thermostat GND Ground HG Hot Gas HPS High Pressure Switch L Line LAR Low Ambient Relay LAT Low Ambient Thermostat LFS Liquid...

Страница 25: ...in a location away from sources of excessive heat and within the specified ambient operating conditions See Technical Specifications for ambient operating conditions IMPORTANT Use this P266 Single Ph...

Страница 26: ...ctronic Pressure Transducer 0 to 52 bar 0 to 754 psi total range with a 1 4 in SAE Female Flare connection and a 2 meter 3 1 ft cable P266xxx x Product P266xxx x Single Phase Condenser Fan Speed Contr...

Страница 27: ...alves filter drier pump down valves fan cycling head pressure controls Process Fluid Components Bronze Y strainer with 20 mesh stainless steel screen Pumps are stainless steel centrifugal Tanks are in...

Страница 28: ...0 0_ 0414 doc PUOD 240 003 0 0 3 Hp 3 Motor ODP Pump with 5 5 Impeller and 0 250 Vane at 3500rpm ASP SSPC Pump Motor Assembly Exploded View If needed the pump label is located on the pump casing near...

Страница 29: ...orts Condensing Area Access Panel Line Voltage Temperature Controller Control Panel PUMP COOL OFF Power Switch High Pressure Reset NOTES Unit should be installed with at least 4 clearance on all sides...

Страница 30: ...it System 2 3 5 2015 SCALE NTS DWG_RefrigerantCircuit Ref Chw ACWC SingleCircuit Typical_0215 vsd SHEET 1 NOTES All specifications and designs are subject to change without notice Hot Gas Bypass optio...

Страница 31: ...SHEET 2 CHILLER PUMP WATER SUPPLY OUT MANUAL BYPASS STAINLESS STEEL TANK WITH SHOE BOX LID WATER RETURN IN DRAIN STAINLESS STEEL COPPER BRAZED PLATE EVAPORATOR TEMPERATURE SENSOR Temperature Controlle...

Страница 32: ...mp PLC Programmable Logic Controller PS Power Supply RC Run Capacitor SW1 Selector Switch Pump Off Cooling SW2 Selector Switch Process Pump SW3 Local Remote Switch TB1 Terminal Block 1 for Internal TB...

Страница 33: ...PLC INPUTS PLC OUTPUTS RED BLK TRAN1 PS 24VDC HPS VIO GRA YLW X1 X0 X2 S S WHT SW1 1 SW1 2 BRN BLU ORN GRN X3 X4 X5 X7 X6 BLK BLK PAGE NOTES 1 Control transformers must be wired tapped for the approp...

Страница 34: ...ontrol with External Supplied Control Voltage 1 2 33 32 OPTION CODE VARIATIONS RS Remote System ON OFF Control with internal supplied 24VDC requiring Dry Contacts RS V Remote System ON OFF Control wit...

Страница 35: ...Notes...

Страница 36: ...MAINTENANCE RECORD DATE PROCEDURE PERFORMED...

Страница 37: ...ll piping is connected properly as appropriate Yes No 12 All chilled water valves are open as appropriate Yes No 13 Crankcase heaters energized for 24 hours before start up Yes No 14 Outdoor piping wr...

Страница 38: ...__________________________________________________________________ __________________________________________________________________________________________________ __________________________________...

Страница 39: ...ight charges to ship these parts EXCLUSIONS The foregoing provisions state the exclusive remedy for any breach of warranty or any other claim in respect to the product described on the reverse side of...

Страница 40: ...s that are not manufacturing defects and are therefore not included in this Limited Warranty 1 Damage to unit or unsatisfactory operation due to improper cleaning or use of unit in corrosive atmospher...

Отзывы: