Addressable Control Panel for CO and NO
2
ZafirCO
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
45
10.3 Configuration
summary
Option 1 of menu 3. In this menu, it is shown the information of sensors configured in each
zone.
S U M M A R Y :
: Z o n e 1
Z o n e 2
Z o n e 3
Z o n e 4
Z O N E S
:
0 0 4 C O :
0 0 3
0 0 4
0 0 3
0 0 5
P O I N T S : 0 1 5 N O 2 :
0 0 0
0 0 0
0 0 0
0 0 0
10.4 Get by programming / Get by point number
Option 1 and 2 of the menu 4. In this menu you can view the information of the points of a zone
ordered by point number (option 1) or by programming number (option 2).
On this information it is possible to modify the program number, add a new point (modifying a
point of a zone with programmation number "0"), delete a point (modifying the programmation
number of the point by the number "0") or introduce the label (through the display of control
panel or the "I-Link CO" program for PC.
The "I Link CO" program is installed on PC with at least Windows 7 operating system, and it
allows writing labels on tables depending on the zone and point number, and download it to the
control panel connecting the PC to the panel with cable USB type A connector on one end (to
connect to the pc) and B type in the other (to connect to the control panel).
Note: When control panel is connected or reseted, it performs a search of the sensors
connected to the zones. If this configuration is accepted, it overwrites the memory
loosing the previous ones. If you want to keep the labels configured, you should not
accept the new configuration. This will be returned to the existing configuration with
their labels, and from here, you should use the options discussed to introduce new
sensors (Add, delete, change).
10.5 Activation
parameters
Option 1 of the menu 5. It allows definition of the concentration values of activation / stop
ventilations and alarm, delay times and means to indicate the average concentration time.
Z n : 0 1
A C T
C O
N O 2
P R E
P S T
Z n : 0 1 & 0 2
V E N T 1
O N
0 5 0
0 1
0 4
0 4
M T : 0 0
[ m n ]
V E N T 2
O F F
1 0 0
0 3
0 4
0 4
A L A R M
O N
2 0 0
0 5
0 1
0 1
Zn:
Selected zone.
VENT1:
Parameters that affects activation/stop of ventilation 1 relay.
VENT2:
Parameters that affects activation/stop of ventilation 2 relay.
ALARM:
Parameters that affects activation/stop of the status and relay of alarm.
ACT
: Show if the values defined under it are actves (ON) or not (OFF). In model with
not "DVB" function, ventilation 2 can not be selected and remain with "OFF" value.
CO:
CO concentration in ppm.
- VENT 1: Selectable between 0 and 300 ppm with 5 ppm increments.
- VENT2: Selectable between VENT1 and 300 ppm with 5 ppm increments.
- ALARM: Selectable between VENT1 or VENT2, and 300 ppm with 5 ppm
increments.
NO
2
:
NO
2
concentration in ppm.
- VENT 1: Selectable between 0 and 20 ppm with 0,1 ppm increments.
- VENT2: Selectable between VENT1 and 20 ppm with 0,1 ppm increments.
- ALARM: Selectable between VENT1 or VENT2, and 20 ppm with 0,1 ppm
increments.