PRE:
Delay to activation or PRE-delay.
- VENT 1: Selectable between 0 and 10 minutes with 1 minute increments.
- VENT2: Selectable between 0 and 10 minutes with 1 minute increments.
- ALARM: Selectable between 0 and 5 minutes with 1 minute increments.
PST:
Delay to stop or PoST-delay.
- VENT 1: Selectable between 0 and 10 minutes with 1 minute increments.
- VENT2: Selectable between 0 and 10 minutes with 1 minute increments.
- ALARM: Selectable between 0 and 5 minutes with 1 minute increments.
MT (Mean Time):
Mean time in minutes used for calculation of average concentration.
It is displayed in working operation (Note: In case of a zone is in alarm status, it is
displayed the instantaneous concentration). It can be selected between 0 minutes
(equivalent to instantaneous measure) and 60 minutes with 5 minutes increments.
10.6 Disable zone / Enable zone
Option 2 and 3 of menu 5. In option 2, selected zone pass to disabled zone. In the option
3, only selected zone pass to work condition. Disabled zone are indicated in control panel
with L, M, N and/or O leds of figure 10.
10.7 Zone in test mode / Active mode
The control panel has two activation modes for zone test, the "individual activation zone" and
the "activation of all zones", which operate independently.
The "individual activation zone" is performed in option 4 and 5 of menu 5. In option 4, only the
selected zone is placed in the test mode by activating the LED L, M, N or O (see Figure 10) with
double flash. In option 5, only the selected test mode zone becomes active in working mode.
If necessary, the control panel has a quick-access "activation of all zones" in test mode using
the "D" key (see Figure 10), which imposes the test mode to all areas of the control panel
activating fixedly the led "D", and off the leds L, M, N and O.
If you leave this mode "activation of all zones" in test mode, the control panel returns to the
previous working state by turning off the LED "D" and activating the proper functioning of the L,
M, N and O leds. This means that if any area was in test mode individually, return to this state.
Therefore, the "D" key is a hotkey that imposes its operation, but once off, returns to the
previous status.
10.8 Edit
zone
Option 6 of menu 5. It is allowed to introduce label for the selected zone with a 7
characters maximum.
10.9 Leds
activation
Option 4 of menu 1. It is allowed 2 options:
1) Active/Desactive permanently a led of a sensor by choosing the zone and selecting /
deselecting the sensor with the "ENTER" key.
2) Active/Desactive permanently the leds of all sensors of one zone, showing the number
of activated sensors.
The activation of the leds remain while this menu is open in the control panel.