Conventional Fire Detection and Fire Alarm
Control Panel
CLVR02EXT
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
33
Indicator leds
are described hereafter:
KEY
LED
COLOUR
DESCRIPTION
Red
Fire alarm due to activation of manual call point or detector.
►
Fixed
Green
System operating through 230 V/AC power supply.
►
Fixed
Green
System operating under batteries.
►
Fixed
Amber
System fault
►
Fixed
Amber
General power supply fault.
►
Fixed
Fault 230V/AC input, batteries input, 30V output, etc
Amber
General sounder output condition
►
Fixed
Relay triggered
►
Intermittent
Fault in the relay, line open, line crossed, sounder fuse
etc.
Amber
Condition of fault output
►
Fixed
Relay triggered
►
Intermittent
Fault in relay, line open, line crossed, fuse fault etc.
Amber
Fault in the auxiliary battery supply
►
fixed
Batteries faulty, discharged or missing.
►
Intermittent
Fault in the battery charger.
Amber
CPU fault
►
Fixed
Control Panel not operating.
Amber
Control Panel communication through RS485 port
►
Intermittent
Control panel communicatin
Amber
Level of access to keyboard of Control Panel.
►
Off
Level 1.
►
Fixed
Level 2.
►
Intermittent
Level 3.
Amber
Silence sounders
►
Fixed
General relay sounder in silent position.
Amber
Disable delays of panel
►
Fixed
Control panel operating without delays at the general sounder
outputs, fault and extinguishing relay “R2”.
Amber
Zone out of service.
►
Fixed
At least 1 zone out of service.
Amber
Zone in test mode
►
Fixed
At least 1 zone in test mode.
Red
Alarm in zone indicated.
►
Fixed
activated by manual call point
►
Intermittent
activated by Detector
Amber
Fault in zone indicated.
►
Fixed
Open line fault.
►
Intermittent
Crossed line fault.
Amber
Zone indicated in test or disabled
►
Fixed
Zone disabled.
►
Intermittent
Zone in test.
Amber
Condition of relay.
►
Fixed
Relay triggered.
►
Intermittent
Relay activated in countdown (only extinguishing relay
R2).
Amber
Relay fault or disabled.
►
Fixed
Relay disabled.
►
Intermittent
Relay fault (Relay fault, line open, line crossed, etc).
Amber
Extinguishing relay locked (R2).
►
Fixed
Activated Emergency abort. Panel may be reset.
►
Intermittent
Extinguishing triggered. Delay time for reset still
countdown.
A
ALARM
Red
Power Supply
B
Bateria / Battery
C
Avería General
General Fault
D
Av. Alimentación
Supply Fault
E
Relé Sirena
Sounder Relay
F
Relé Avería
Fault Relay
G
Avería Batería
Battery Fault
H
Avería CPU
CPU Fault
I
J
COM
Acceso Teclado
Keyboard Access
K
sin Retardo
no delay
M
desconexión
general disable
N
modo pruebas
test mode
O
L
ALARM
P
AVERÍA / FAULT
PRUEBA / ANULADO
TEST / DISABLED
R
Q
R1 R2
1
S
T
U
BLOQUEO RELÉ
RELAY LOCKED
DISPARO RELÉ
RELAY TRIGGER
AVERÍA / ANULADO
FAULT / DISABLED