Conventional Fire Detection and Fire Alarm
Control Panel
CLVR02EXT
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
56
10. Reference of software version and configuration version of delays in
the control panel
The CLVR control panel has references for the CPU software version as well as the delay
configuration version. The CPU software version is inserted by the manufacturer.
For its part, the delay configuration version counts the number of times that the delays are
configured on the control panel. This function allows control to be taken by the
installer/maintainer for handling the control panel.
To consult these versions, follow the procedure below:
1) Activate access level 2 (press the control keys once in the following order: Zone
Selection, Reset/Autotest, Zone Selection, Reset/Autotest).
2) Activate access level 3 (press the control keys once in the following order: Test mode,
Disable, Test mode, Disable).
3) Select the control key
reset/autotest
Initially, the control panel will respond by illuminating all the LEDs and the buzzer.
Afterwards all the LEDs will go out, and using the same indication leds used for configuring the
time delay (see figure 8) used in binary code, the software version will be indicated.
Subsequently they will switch off, and the delay configuration version with the same mode as
the software version will be shown.
Finally, all these indicators will go out, and the control panel will go into standby.
Figure 17: Keys and indicators used to reference the version of software and the delay configuration
software version