Conventional Fire Detection and Fire Alarm
Control Panel
CLVR02EXT
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
43
6 Access levels to the control panel
The control panel has 3 access levels. The following table shows the order for pressing the
control keys and the functionality available in the different access levels. To access level 3, first
activate level 2.
NOTE:
The number appearing on the
control key corresponds to its
description in chapter 2.1.2. and
NOT
to the number of times it must
be pressed.
Figure 7: Keys used in the control panel access levels CLVR02EXT
Access level
Key combination
(order of pressing)
Functionality
1
None
Stop buzzer
2
Level 1 actions
Stop
sounders
No
delay
Disable
zones/relays
Zone test mode
3
Level 2 actions
Configuration of delays.
Reference of software version
and configuration version of
delay configuration.
If no key is pressed, the access state will be abandoned after 30 seconds
In all control panels, the Stop buzzer key is the only one which can be used in level 1