Electrovalves circuit identification
Block this tube
To the pump input are connected 2 tubes, one goes to
EV1
and
2
and the other one to
EV3
and
4
.
Make the test, bending the tube that goes towards
EV 3
and
4
as shown in the image.
If after blocking the tube the vacuum loss persists, proceed replacing the CPU, since possibly the
vacuum sensor is faulty.