EVAC-500 Voice Alarm & Evacuation System Operation Manual
5
/
42
4
-
Fault Indicator.
Off means system working well unless the dipswitch PIN of all supervision function is disable on rear panel; yellow
means system fault, otherwise press “ACK/REST” to restore the system.
5-Emergency Microphone Indicator
.
Yellow----means emergency microphone lost or faulty; Green----means working well; extinguish----means microphone
is normal but it is not working.
6-Indication Test Button
.
Press the button to light on the LED indicators of all equipments include host, extension and paging microphone to test
the indication working well.
7-Emergency Button.
Red flash—emergency mode; extinguish--normal mode.
Making Emergency Broadcast:
a) Emergency broadcast will be activated by manual press the button and red light flashing.
b) Auto emergency broadcast will be activated by the trigger inputs on the rear panel of host and extension unit and red
light flashing.
Reset the Emergency Mode:
a) Press the “ACK/Reset” button on the front panel to exist the emergency mode to terminate the emergency broadcast
and terminate the zone output.
b) Input a reset signal to the emergency control input terminal on the rear panel of the EVAC-500 which has been
assigned a reset function. These events history could be recorded and inquired in the software history record.
8-ACK/RESET Button
a). If the system various modules work normal or abnormal system module diagnosis but press the button when the
indicator "FAULT" light is not flashing, equipment do not do any processing,
b). If the system module in the diagnosis of abnormal, "FAULT" of FAULT indicator light flashing, press some button,
"FAULT" stopped lighting from blinking, blinking indicating its disabled state ,Buzzer to stop till To the new module
detects abnormal after heavy shine again "FAULT" LED lamp and start the buzzer hint user,
c). When the current partition has output, press the build close the current audio output, quick exit and quit play.
9 & 10-EVAC MSG & ALERT MSG
Green——“EVAC MSG/ALERT MSG” Voice is in broadcast information
;
Yellow——“EVAC MSG/ALERT MSG” Lose
voice information or loss SD card
;
Extinguish—— “EVAC MSG/ALERT MSG” Normal.
Note:
1."EVAC voice information" refers to the EVAC voice ALERT and voice
;
2. If you need to manually play EVAC
voice messages
,
Need to enter the emergency mode, Then press the voice messages button; 3. System default
“EVAC” Voice priority is higher than "ALERT". Can change the priority through the EVAC - 500 SFT configuration..If not
special application requirements, please do not change it.
11-Line Input Selector
Mainly used to select the external line input to this host or extension.
Only the host audio tracks can be output to the extension of the host while line extension of the host audio won't scale