4.6 Recommended
connection
The installer must define:
•
component type
•
position in system
2
7
9
13
3
1
14
UNIT
6
10
12
4
5
8
15
F
11
1
antivibration joints
9
safety valve
2
piping support
10
Flow Switch
3
exchanger chemical cleaning bypass
11
pressure gauge
4
drain valve
12
thermometer
5
vent
13
filter
6
shut-off valve
14
Internal storage tank
7
Pump / circulating pump
15
Cleaning system bypass
8
expansion vessel
4.7 Hydraulic
connections
•
take away the supplied connection union by acting on the connection joint
•
weld the union to the installation pipe
•
perform the connection between the installation pipe and the evaporator, using the joint
Retirer le joint de connexion avant de souder le tuyau de l’installation.
The rubber gasket might be irreparably damaged.
4.8 Water
filter
Use filter with mesh pitch:
1,6 mm
It must be installed immediately in the water input of the unit, in a position that is easily accessible for cleaning.
The filter never should be removed, this operation invalidates the guaranty.
4.9 Flow
Switch
The flow switch must be present to ensure shutdown of the unit if water is not circulating.
It has to be installed in a duct rectilinear part, not in proximity of curves that cause turbulences.
A
!
A
A > 5 Ø
Ø
A.
minimum
distance
Содержание WSAN-XSC3 MF 200.4
Страница 20: ...20 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 6 4 Configuration for 2 pipe system ...
Страница 45: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 45 8 17 Compressor replacement ...
Страница 46: ...46 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 8 18 Exchanger replacement ...
Страница 47: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 47 9 Accessories 9 1 Anti vibration mount support ...
Страница 48: ...48 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 ...