Configuration for 4-pipe system
Acoustic configuration: super-silenced (EN)
General technical data - Performance
Size
90.4
100.4
110.4
120.4
140.4
160.4
180.4
200.4
220.4
240.4
Cooling
Cooling capacity
1
[kW]
248
263
288
326
369
413
481
524
574
618
Compressor power input
1
[kW]
82,4
89,3
98,6
115
129
143
166
179
199
224
Total power input
2
[kW]
89,4
96,3
106
122
138
152
178
191
211
235
EER
1
-
2,78
2,73
2,72
2,67
2,68
2,72
2,71
2,75
2,72
2,63
Water flow-rate
1
[l/s]
11,9
12,6
13,7
15,6
17,6
19,7
23,0
25,0
27,4
29,5
Cold user side exchanger pressure drops
1
[kPa]
36,7
40,9
41,4
39,9
42,5
41,5
36,7
43,3
39,9
46,0
Cooling capacity (EN14511:2013)
3
[kW]
248
262
287
307
367
412
479
522
572
616
Total power input (EN14511:2013)
3
[kW]
90,2
97,2
107
123
139
153
179
192
213
237
EER (EN 14511:2013)
3
-
2,74
2,70
2,69
2,50
2,65
2,68
2,68
2,72
2,69
2,60
ESEER (EN 14511:2013)
3
-
4,16
4,26
4,24
4,24
4,19
4,29
4,22
4,30
4,30
4,21
Cooling capacity (AHRI 550/590)
7
[kW]
247
262
286
325
367
411
480
522
572
616
Compressor power input (AHRI 550/590)
7
[kW]
82,2
89,1
98,4
115
128
142
166
179
199
223
Total power input (AHRI 550/590)
7
[kW]
89,2
96,1
106
122
137
151
178
191
211
234
COPr
7
-
2,77
2,73
2,70
2,66
2,68
2,72
2,70
2,73
2,71
2,63
IPLV
7
-
4,65
4,78
4,74
4,75
4,68
4,78
4,71
4,83
4,82
4,73
Heating
Heating capacity
4
[kW]
295
326
355
395
445
492
567
627
675
728
Compressor power input
4
[kW]
72,3
79,9
87,3
97
108
120
140
155
171
184
Total power input
2
[kW]
81,9
89,5
97
106
121
133
156
171
187
200
COP
4
-
3,60
3,64
3,66
3,72
3,69
3,70
3,64
3,67
3,61
3,64
Water flow-rate
4
[l/s]
14,1
15,6
17,0
18,9
21,3
23,5
27,1
30,0
32,3
34,8
Hot user side exchanger pressure drops
4
[kPa]
40,2
47,9
38,3
46,6
35,4
42,9
31,8
38,8
45,2
46,2
Heating capacity (EN14511:2013)
5
[kW]
296
327
356
397
446
494
568
629
677
731
Total power input (EN14511:2013)
5
[kW]
82,9
90,8
98
108
122
135
157
173
189
203
COP (EN 14511:2013)
5
[kW]
3,57
3,60
3,63
3,68
3,66
3,67
3,62
3,64
3,58
3,61
Cooling 100% - Heating 100%
Cooling capacity
6
[kW]
255
275
305
344
397
442
509
556
612
670
Heating capacity
6
[kW]
331
357
396
447
513
573
658
720
794
866
Total power input
6
[kW]
76,6
82,6
91,2
103
117
132
150
164
183
197
Global efficiency
8
[kW]
7,65
7,64
7,69
7,66
7,76
7,68
7,80
7,76
7,70
7,79
The Product is compliant with the ErP (Energy Related Products) European Directive. It includes the Commission delegated Regulation (EU) No 811/2013 (rated heat output ≤ 70 kW at specified reference conditions) and the Commission
delegated Regulation (EU) No 813/2013 (rated heat output ≤ 400 kW at specified reference conditions)
1. Data referred to the following conditions: internal exchanger water = 12/7 °C. Entering external exchanger air temperature 35°C. Internal exchanger fouling factor = 0.44 x 10^(-4) m² K/W. Considering cooling only operation.
2. The Total Power Input value does not take into account the part related to the pumps and required to overcome the pressure drops for the circulation of the solution inside the exchangers
3. Data compliant to Standard EN 14511:2013 referred to the following conditions: - Internal exchanger water temperature = 12/7°C - Entering external exchanger air temperature = 35°C. Considering cooling only operation.
4. Data referred to the following conditions: internal exchanger water = 40/45 °C. Entering external exchanger air temperature = 7°C D.B./6°C W.B. Internal exchanger fouling factor = 0.44 x 10^(-4) m² K/W. Considering heating only
operation.
5. Data compliant to Standard EN 14511:2013 referred to the following conditions: - Internal exchanger water temperature = 40/45 °C. Entering external exchanger air temperature = 7°C D.B./6°C W.B. Considering heating only operation.
6. Data referred to the following conditions: exchanger water cooling side = 12/7 °C. exchanger water heating side = 40/45°C. Exchanger fouling factor = 0.44 x 10^(-4) m² K/W
7. Data compliant to Standard AHRI 550/590 referred to the following conditions: internal exchanger water temperature = 6,7 °C. Water flow-rate 0,043 l/s per kW. Entering external exchanger air temperature 35°C. Internal exchanger
fouling factor = 0.18 x 10^(-4) m2 K/W. Considering cooling only operation.
8. Global Efficiency = (Cooling ca Heating capacity) / Total power input
Содержание WSAN-XSC3 MF 200.4
Страница 20: ...20 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 6 4 Configuration for 2 pipe system ...
Страница 45: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 45 8 17 Compressor replacement ...
Страница 46: ...46 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 8 18 Exchanger replacement ...
Страница 47: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 47 9 Accessories 9 1 Anti vibration mount support ...
Страница 48: ...48 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 ...