Configuration for 2-pipe system
Admissible water flow-rates
Minimum (Qmin) and maximum (Qmax) admissible water flow for the unit to operate correctly.
User side exchanger
EXCELLENCE SC/EN
90.4
100.4
110.4
120.4
140.4
160.4
180.4
200.4
220.4
240.4
Qmin
[l/s]
7,4
7,4
8,0
9,3
10,1
11,5
14,3
14,3
16,4
16,4
Qmax
[l/s]
20,0
20,0
21,8
25,1
27,5
31,2
38,6
38,6
44,0
44,0
Recovery exchanger
EXCELLENCE SC/EN
90.4
100.4
110.4
120.4
140.4
160.4
180.4
200.4
220.4
240.4
Qmin
[l/s]
8,5
8,5
10,4
10,4
13,6
13,6
18,6
18,6
19,2
19,8
Qmax
[l/s]
22,7
22,7
22,7
22,7
36,3
36,3
48,3
48,3
49,8
51,4
Overload and control device calibrations
open
closed
value
High pressure safety pressure switch
[kPa]
4050
3300
-
Antifreeze protection
[°C]
3
5.5
-
High pressure safety valve
[kPa]
-
-
4500
Low pressure safety valve
[kPa]
-
-
2950
Max no. of compressor starts per hour
[n°]
-
-
10
High compressor discharge temperature safety thermostat
[°C]
-
-
140
Exchanger operating range
Internal exchanger
DPr
DPw
PED (CE)
4500
4500
1000
DPr = Maximum operating pressure on refrigerant side in kPa
DPw = Maximum operating pressure on water side in kPa
Содержание WSAN-XSC3 MF 200.4
Страница 20: ...20 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 6 4 Configuration for 2 pipe system ...
Страница 45: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 45 8 17 Compressor replacement ...
Страница 46: ...46 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 8 18 Exchanger replacement ...
Страница 47: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 47 9 Accessories 9 1 Anti vibration mount support ...
Страница 48: ...48 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 ...