6.9 Remote controls
Check that the remote controls (ON-OFF etc) are connected and, if necessary, enabled with the respective parameters as indicated in the
“electrical connections” section.
Check that probes and optional components are connected and enabled with the respective parameters (“electrical connections” section and
following pages).
6.10 Options
Menu accessible only after having entered the password.
Access reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
Path: Main menu / Unit parameters / Options
Parameters
Short description
description
P0050
En Demand limit
Enabling Demand Limit: 0 = disabled, 1 = analogic input, 2 = parameter
P0051
En Water reset
Enabling Water reset: 0 = Off, 1 = Cool, 2 = Heat, 3 = Cool and Heat
P0052
En 2SetPoint
Enabling 2SetPoint: 0 = Off, 1 = On
P0053
En Climatica
Enabling Climatic TExt: 0 = Off, 1 = Cool, 2 = Heat, 3 = Cool and Heat
P0054
PrioritaCmd
Status and machine mode priority: Local [0] = Priority to local commands, BMS [1] priority to commands from plant
supervisor
P0055
En DI On-Off
Enabling remote ON-OFF: 0 = Off, 1 = On
P0061
Enable scheduler
Enabling scheduler: 0 = Off, 1 = On
P0062
TypeDL
Inlet signal type: 0 = 0-10V; 1 = 4-20mA
P0063
TypeWR
Inlet signal type: 0 = 0-10V; 1 = 4-20mA
6.11 Evaporator water flow-rate
Check that the difference between the temperature of exchanger return and supply water corresponds to power according to this formula:
unit cooling power (kW) x 860 = Dt (°C) x flow rate (L/h)
The cooling power is shown in the table of the GENERAL TECHNICAL DATA included in this manual, referred to specific conditions, or in the
tables on COOLING PERFORMANCE in the TECHNICAL BULLETIN referred to various conditions of use.
Check for water side exchanger pressure drops:
determine the water flow rate
measure the difference in pressure between exchanger input and output and compare it with the graph on WATER SIDE EXCHANGER
PRESSURE DROPS
The measurement of pressure will be easier if pressure gauges are installed as indicated in the DIAGRAM OF SUGGESTED WATER CONNECTIONS.
6.12 Start-up report
Identifying the operating objective conditions is useful to control the unit over time.
With unit at steady state, i.e. in stable and close-to-work conditions, identify the following data:
•
total voltages and absorptions with unit at full load
•
absorptions of the different electric loads (compressors, fans, pumps etc)
•
temperatures and flows of the different fluids (water, air) both in input and in output from the unit
•
temperature and pressures on the characteristic points of the refrigerating circuit (compressor discharge, liquid, intake)
The measurements must be kept and made available during maintenance interventions.
Содержание WDAT-iL3 250.2
Страница 9: ...M04Z40C18 02 WDAT iL3 250 2 580 2 9 3 5 AxiTop...
Страница 39: ...M04Z40C18 02 WDAT iL3 250 2 580 2 39 8 16 Compressor replacement...
Страница 41: ...M04Z40C18 02 WDAT iL3 250 2 580 2 41...
Страница 42: ...42 WDAT iL3 250 2 580 2 M04Z40C18 02...
Страница 43: ...M04Z40C18 02 WDAT iL3 250 2 580 2 43...
Страница 57: ...57 Page intentionally left blank...