![CLIVET WDAT-iL3 250.2 Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/clivet/wdat-il3-250-2/wdat-il3-250-2_installation-and-operating-manual_2625549049.webp)
M04Z40C18-02
WDAT-iL3 250.2-580.2
49
Admissible water flow-rates
Minimum (Qmin) and maximum (Qmax) admissible water flow for the unit to operate correctly.
PREMIUM SC
250.2
280.2
320.2
360.2
400.2
420.2
440.2
480.2
540.2
580.2
Qmin
[l/s]
15,3
20,1
20,1
21,6
39,4
39,4
39,4
32,3
32,3
32,3
Qmax
[l/s]
37,3
45,2
45,2
53,4
86,6
86,6
86,6
72,5
72,5
72,5
Exchanger operating range
Internal exchanger
DPr
DPw
PED (CE)
2450
1050
DPr = Maximum operating pressure on refrigerant side in kPa DPw = Maximum operating pressure on water side in kPa
Overload and control device calibrations
open
closed
value
High pressure switch
[kPa]
2000
1450
–
Antifreeze protection
[°C]
3
5.5
–
High pressure safety valve
[kPa]
–
–
2400
Low pressure safety valve
[kPa]
–
–
1650
Max no. of compressor starts per hour
[n°]
–
–
6
Discharge safety thermostat
[°C]
–
–
120
Содержание WDAT-iL3 250.2
Страница 9: ...M04Z40C18 02 WDAT iL3 250 2 580 2 9 3 5 AxiTop...
Страница 39: ...M04Z40C18 02 WDAT iL3 250 2 580 2 39 8 16 Compressor replacement...
Страница 41: ...M04Z40C18 02 WDAT iL3 250 2 580 2 41...
Страница 42: ...42 WDAT iL3 250 2 580 2 M04Z40C18 02...
Страница 43: ...M04Z40C18 02 WDAT iL3 250 2 580 2 43...
Страница 57: ...57 Page intentionally left blank...