M04Z40C18-02
WDAT-iL3 250.2-580.2
27
7.4 Change unit state
Step Action
Menu/Variable
Keys
Display
1
Press
Main menu
2
Select
Cmd Local state
3
Set
OFF - ECO - ON - Pump On
4
Confirm
6
Exit
STATE
ON
Compressors enabled
OFF
Compressors disabled
Antifreeze protection user side active
ECO
Compressors enabled
Pumps activated periodically
Setpoint = SetPoint ECOCool
Pmp_On
Compressors disabled
Pumps running
7.5 Modify setpoint
Step Action
Menu/Variable
Keys
Display
1
Press
Main menu
2
Select
Unit parameters
Unit parameters
3
Confirm
Set Point
4
Select
Set Point
5
Set
Set Point
6
Confirm
7
Exit
Parameters
Short description
description
P0001
SetPoint Cool
Setpoint Cool
P0003
2°SetPoint Cool
2° Setpoint Cool
Enable by remote switch
P0005
SetPoint ECOCool
Economic summer SetPoint