21
English 01/07
ACCURATE AX* - AW*
Check the room temperature setting (see the
control panel manual).
The parameter settings on the microprocessor
controller are not correct.
Verificare la consistenza del carico latente.
Latent load lower than expected.
Check the pressure of the supply water;
Check the operation of the manual control
system and the steam production unit (see the
control panel manual)
The humidifier isn't working.
See the control panel manual; check the
operation of the panel and/or the probe.
The control system isn't working.
AMBIENT HUMIDITY
TOO LOW
FAULT
CAUSE
SOLUTION
Check the power supply to the fans.
The fans are not powered.
Clean the filter using a vacuum cleaner after
having shaken off the larger particles of dust.
Replace the filter if excessively clogged.
Check the correct calibration of the dirty filter
differential pressure switch F4.
The filters are blocked (possible activation of
the dirty filter alarm).
See the paragraph on AIR DISTRIBUTION
Obstructions to the air flow.
Check the resistance of the fan windings; after
resetting, measure the voltage and power
input.
The fan thermal cutout has tripped.
EC radial fan speed set too low
Check the sizing of the air distribution system
(ducting, false-ceiling, underfloor plenum, grills)
Excessive pressure drop in the air distribution
system.
LOW OR NO AIR
FLOW
See “LOW OR NO AIR FLOW”.
Insufficient air flow-rate
Check the continuity of the connection from
the safety thermostat to the control system.
Thermostat connection wire cut or broken
Replace the heater safety thermostat.
Faulty thermostat
HEATER SAFETY
THERMOSTAT
ACTIVATED