11
English 01/07
ACCURATE AX* - AW*
CALIBRATING THE PRESSURE CONTROL VALVE
A
I
U
(option available for water-cooled models)
The pressure control valve, by managing the flow of water, pre-
vents the condensing pressure from lowering excessively and, at
the same time, saves water consumption.
If necessary, calibrate the pressure control valve using the adjust-
ment knob (the pressure is increased when turning clockwise)
until the condensing pressure stabilises at the recommended
value of 17 bar (equivalent to a saturated temperature of around
45°C when using R22), measured using a pressure gauge connect-
ed to the pressure test point on the outlet valve.
1
2
3
4
5
CALIBRATING THE CONTROL AND SAFETY DEVICES
A
I
U
After starting the air-conditioner, make the following adjustments
- Room temperature (cooling and heating set point).
- Relative humidity (set point for humidification and dehumidifi-
cation);
- Dirty filter differential pressure switch: see the paragraph on
"CALIBRATING THE DIRTY FILTER SENSOR".
The calibration values of the control and safety devices must not
be altered.
Symbol
Description
F1
High pressure switch
F2
Low pressure switch
TH1
Safety thermostat (versions T and H)
Symbol Activation
Differential Reset
F1
28 bar (opening)
-
Manual reset
F2
1,5 bar (opening)
1.5 bar
2.5 bar (automatic)
TH1
320 °C (opening)
-
Manual reset