22
English 01/07
ACCURATE AX* - AW*
Empty and recharge the circuit.
A) Air or incondensable gas in the refrigerant
circuit, seen by the presence of bubbles, despite
measuring a high subcooling.
Check the operation and the correct direction
of rotation of the fans on the outdoor heat
exchanger.
Check that the exchanger is not dirty and
remove any material that may be blocking it
(leaves, paper, seeds, dust, etc.) with a jet of
compressed air or with a brush;
Check the outdoor unit for any obstacles to
the flow of air and any recirculation of the coo-
ling air;
Check that the temperature of the cooling air
does not exceed the design value.
B) Insufficient air flow-rate to the remote heat
exchanger or air too hot
Check the flow-rate, the pressure and the
temperature of the cooling water in the clo-
sed circuit;
Check the calibration and the operation of the
pressure control valve.
Insufficient water flow-rate to the condenser
or water too hot.
Remove refrigerant from the circuit.
Excessive refrigerant charge; condenser
partially flooded. Excessive subcooling of the
liquid at the condenser outlet.
Check the opening of the valves.
Valves on the high pressure side of the circuit
partially closed.
HIGH COMPRESSOR
DISCHARGE
PRESSURE
FAULT
CAUSE
SOLUTION
Check the operation of the condenser fans
and the corresponding protection device;
repair or replace the faulty fans;
Check the calibration and the operation of the
remote condenser fan pressure switch or the
speed controller.
(See CONTROLLING THE CONDENSING
PRESSURE)
The condensing pressure control system
isn't working.
See “HIGH COMPRESSOR DISCHARGE
PRESSURE”.
The system is affected by an excessive
discharge pressure
HIGH PRESSURE
SWITCH ACTIVATED
(high compressor
discharge pressure)
Check the calibration and the operation of the
condenser fan pressure switch or the speed
controller;
The condensing pressure control system
isn't working (see the control panel manual).
Check the temperature of the cooling water;
Check the calibration and the operation of the
pressure control valve (if fitted);
Install a pressure control valve to manage the
flow-rate of water according to the conden-
sing pressure.
Excessive water flow-rate to the condenser
or water too cold.
See “LOW COMPRESSOR SUCTION
PRESSURE”.
Suction pressure too low
LOW COMPRESSOR
DISCHARGE
PRESSURE