![CLIMAVENETA ACCURATE Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/climaveneta/accurate/accurate_user-and-maintenance-manual_2624836021.webp)
19
English 01/07
ACCURATE AX* - AW*
TERMINAL AND BOARD CONFIGURATION
A
I
U
TROUBLESHOOTING
A
I
U
FILL AND DRAIN ASSEMBLIES
To ensure the correct operation of the humidifier, the supply/fill and
drain assemblies need to be inspected periodically.
Proceed as follows:
- completely drain the water from the boiler using the MANUAL
CONTROLS on the controller A1;
- disconnect the power supply by opening the main switch on the
electrical panel;
- remove the fill pipe from the 3/4 GAS fitting on the fill solenoid
valve;
- remove and clean the filter located inside the solenoid valve fit-
ting;
- dismantle the drain assembly (shown in Figure 13), clean the pipes
and remove any flakes of scale from the cup-drain trap.
Check for voltage; close the main switch.
The electrical panel is not powered
Check that the cutout IM in the auxiliary cir-
cuits is armed.
Check the fuse on the main board.
The auxiliary circuits are not powered
Check for DC power.
The control panel does not start the
air-conditioner.
FAULT
CAUSE
SOLUTION
THE AIR-CONDITIO-
NER DOESN'T START
See the controller manual.
The parameter settings on the microprocessor
controller are not correct.
See “LOW OR NO AIR FLOW”.
The air flow-rate is too low or null.
Check the electrical connections and the
configuration of the controller.
The probe isn't working.
Check the thermal load in the room being
air-conditioned.
Thermal load higher than expected.
Check the electrical connections to the valve
servomotor. Open the valve using the manual
control knob.
Three-way valve not working.
Check for the flow of chilled water; check that
any on-off valves outside of the unit are open.
No flow of chilled water.
Check the operation of the water chiller.
High temperature of the chilled water.
See “THE COMPRESSOR/COMPRESSORS
DON'T START”.
The compressor/compressors don't start,
despite being activated by the controller.
ROOM TEMPERATURE
TOO HIGH
Troubleshooting is simplified by the information provided by the
microprocessor controller: if an alarm is signalled, refer to the
control panel instruction manual.
If required, contact the nearest service centre, indicating the
probable causes of the fault.
Содержание ACCURATE
Страница 2: ......
Страница 26: ...24 English 01 07 ACCURATE AX AW ...
Страница 27: ......
Страница 28: ...Dé Longhi Group Via L Seitz 47 31100 Treviso Italia COD 5787001000 ...