13
English 01/07
ACCURATE AX* - AW*
WARNING: Disconnect power before working on the
servomotor
On the units with
ACCURATE
controllers the position of the
servomotor is proportional to the control voltage, between 0
and 10 Vdc.The servomotor stops:
- automatically at the end of its travel;
- in the position of equilibrium, corresponding to the control
voltage;
- in the current position, when cutting off power.
OPERATION OF THE MVX57 - 0-10V SERVOMOTORS
The opening of the valve can be controlled by checking the posi-
tion using the indicator located on the top of the servomotor
EMERGENCY MANUAL OPERATION
The valve can be operated manually, in the event of faults to the
servomotor or the control system, using the manual control
knob located near the servomotor.
TEMPERATURE AND HUMIDITY PROBE
A
I
U
The figure shows the optional temperature and humidity probe.
If having to replace the probe, release the white plastic cover by
pressing point (A) with a screwdriver or a pointed object; lift the
cover (B) to access the fastening screws (C) and the terminals
(D).
For the probe electrical connection use a shielded cable; the con-
nections to the terminals on the board are shown on the wiring
diagram.
126
mm
80
A
B
H
T
U
O
M
T
T
U
O
+
C
D
Shielded cable
inlet
Fastening
holes
SERVOMOTOR AND HOT WATER VALVE
A
I
U
2
IN
OUT