Valve connections
The connections of the valves to the fan coil are illus-
trated on page 37-53.
The positions of the coil manifolds are shown on page
19-21.
Two- or three-way valves
The valves are supplied with the connecting pipes and
must be fitted by the installer.
The elbows are connected to the fan coil using flared
joints fitted with flat gaskets.
Valve characteristics:
Type:
-
a-CXW 0402-0502-0602-0702
i-CXW 0502-0602-0702
Main coil
-
a-CXW 0404-0504-0604-0704
i-CXW 0504-0604-0704
Main and auxiliary coil
-
a-CXW 0804-1104-1204
i-CXW 0804-1104
Auxiliary coil
No. of ways
KVS
m³/h
ΔPmax*
kPa
Valve
fittings**
2
2.8
50
3/4”
3
2.5
50
3/4”
Type:
-
a-CXW 0802-1102-1202
i-CXW 0802- 1102
Main coil
-
a-CXW 0804-1104-1204
i-CXW 0804-1104
Main coil
No. of ways
KVS
m³/h
ΔPmax*
kPa
Valve
fittings**
2
5.2
60
1”
3***
4.5
50
1”
* Maximum differential pressure with valve closed
** External thread
*** Conical seal for Honeywell valves
Water flow control kit with 2- or 3-way ON-OFF valves
with thermoelectric actuator.
Note:
The maximum pressure drop through the ful-
ly-open valve should not exceed 25 kPa in cooling
mode and 15 kPa in heating mode.
WATER CONNECTION