![CLIMAVENETA a-CXW 1102 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/climaveneta/a-cxw-1102/a-cxw-1102_user-and-installation-manual_2624835014.webp)
14
EN
TECHNICAL SPECIFICATIONS
i-CXW 4-pipe system
1 Room temperature 27°C d.b. / 18.9°C w.b.; Chilled water (in/out) 7°C/12°C.
2 Room temperature 20°C d.b.; Hot water (in/out) 45°C/40°C.
3 Sound pressure level in an essentially free field on a reflecting floor, 1 m in front of the fans and 1 m above the floor.
Non-binding value obtained from the sound power level.
4 Sound power based on measurements performed in accordance with ISO 3741 and Eurovent 8/2.
5 Unit in standard configuration and construction, without optional accessories.
6 Values refer to EN 14511
7 Values refer to [REGULATION (EU) No. 2016/2281]
Certified data in EUROVENT
i-CXW
504
604
704
804
1104
ELECTRICAL DATA
Power supply
V/ph/Hz
230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
2 PIPES SYSTEM CONFIGURATION
ENERGY EFFICIENCY
COOLING (EN14511 VALUE)
FCEER
(1)(6)
kW/kW
309
295
202
354
273
FCEER Class
A
A
A
A
A
HEATING ONLY (EN14511 VALUE)
FCCOP
(2)(6)
kW/kW
362
244
164
454
254
FCCOP Class
A
B
B
A
B
PERFORMANCE
MIN SPEED
Fan Power Input
-1
W
5,37
5,72
6,57
9,96
10,7
Air flow rate
-1
m³/h
310
310
360
630
710
Total capacity in cooling mode
-1
kW
1,85
2,09
2,37
4,29
4,97
Total Net Cooling Capacity
(1)(6)(7)
kW
1,85
2,09
2,36
4,28
4,96
Sensible capacity in cooling mode
-1
kW
1,34
1,49
1,7
3,08
3,51
Net sensible cooling capacity
(1)(6)(7)
kW
1,33
1,48
1,69
3,07
3,5
Net latent power in cooling
(1)(6)(7)
kW
0,51
0,6
0,67
1,21
1,46
Max water flow
-1
m³/h
0,09
0,1
0,11
0,21
0,24
Pressure Drop in cooling mode
-1
kPa
4,8
3,9
5
10,9
8,1
Total capacity (heating mode)
-2
kW
2,13
1,73
1,92
5,4
4,57
Total Net Heating Capacity
(2)(6)
kW
2,14
1,74
1,92
5,41
4,58
Water flow in heating mode
-2
m³/h
0,05
0,04
0,05
0,13
0,11
Pressure drop in heating mode
-2
kPa
4,9
2,8
3,4
9,2
5,3
Sound Pressure
-3
dB(A)
24
24
28
24
25
Sound Power
(4)(7)
dB(A)
33
33
37
33
34
MED SPEED
Fan Power Input
-1
W
7,54
10,3
21,9
17,2
31,3
Air flow rate
-1
m³/h
380
445
610
870
1130
Total capacity in cooling mode
-1
kW
2,17
2,82
3,53
5,27
7,16
Total Net Cooling Capacity
(1)(6)(7)
kW
2,16
2,81
3,51
5,26
7,13
Sensible capacity in cooling mode
-1
kW
1,6
2,04
2,62
3,83
5,2
Net sensible cooling capacity
(1)(6)(7)
kW
1,59
2,03
2,6
3,81
5,17
Net latent power in cooling
(1)(6)(7)
kW
0,57
0,78
0,91
1,44
1,96
Max water flow
-1
m³/h
0,1
0,13
0,17
0,25
0,34
Pressure Drop in cooling mode
-1
kPa
6,4
6,8
10,2
15,9
15,6
Total capacity (heating mode)
-2
kW
2,5
2,19
2,64
6,64
6,24
Total Net Heating Capacity
(2)(6)
kW
2,51
2,2
2,66
6,66
6,27
Water flow in heating mode
-2
m³/h
0,06
0,05
0,06
0,16
0,15
Pressure drop in heating mode
-2
kPa
6,5
4,3
6
13,2
9,1
Sound Pressure
-3
dB(A)
30
34
41
30
38
Sound Power
(4)(7)
dB(A)
39
43
50
39
47
MAX SPEED
Fan Power Input
-1
W
16,1
31,1
61,7
33
108
Air flow rate
-1
m³/h
535
710
880
1165
1770
Total capacity in cooling mode
-1
kW
2,76
3,93
4,53
6,51
9,86
Total Net Cooling Capacity
(1)(6)(7)
kW
2,75
3,9
4,47
6,48
9,76
Sensible capacity in cooling mode
-1
kW
2,08
2,95
3,46
4,83
7,4
Net sensible cooling capacity
(1)(6)(7)
kW
2,06
2,92
3,4
4,8
7,29
Net latent power in cooling
(1)(6)(7)
kW
0,68
0,98
1,07
1,68
2,46
Max water flow
-1
m³/h
0,13
0,19
0,22
0,31
0,47
Pressure Drop in cooling mode
-1
kPa
10
12,5
16,1
23,3
28
Total capacity (heating mode)
-2
kW
3,16
2,88
3,23
8,21
8,22
Total Net Heating Capacity
(2)(6)
kW
3,18
2,91
3,29
8,24
8,33
Water flow in heating mode
-2
m³/h
0,08
0,07
0,08
0,2
0,2
Pressure drop in heating mode
-2
kPa
9,8
6,9
8,5
19
14,8
Sound Pressure
-3
dB(A)
38
45
51
39
48
Sound Power
(4)(7)
dB(A)
47
54
60
48
57
SIZE AND WEIGHT
A
-5
mm
575
575
575
820
820
B
-5
mm
575
575
575
820
820
H
-5
mm
275
275
275
303
303
Operating weight
-5
kg
22
24
24
36
39
Содержание a-CXW 1102