CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tranquility
®
(TRL) Series
R e v. : N o v e m b e r 1 1 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
8
Unit Physical Data
Tranquility
®
(
TRL
)
Series
(
60 Hz
)
Model
TRL006
TRL009
TRL012
TRL015
Factory Charge R410A - (oz.)
19
19
26
28
Motor & Blower
ECM Constant Torque (HP) [W]
0.25 [186]
Blower Wheel Size (Dia x W)
5.7 x 7.98 (1pc)
5.7 x 7.98 (2pc)
Water Connection Size
Water volume (gal)*
0.037
0.042
0.049
FPT - All Other
1/2” FPT
Horizontal
Filter Standard - 1” Throwaway
8.5 x 28 x 1
Filter Standard - 2” Throwaway
8.5 x 28 x 2
Weight - Operating (lbs.)
145
146
152
159
Weight - Packaged (lbs.)
185
186
192
199
*Volume for BPHE only
Unit Maximum Water Working Pressure
Max Pressure PSIG
[kPa]
Base Unit
500 [3447]
Internal Secondary Pump (ISP)
200 [1379]
Internal Motorized Water Valve (MWV)
300 [2068]
Internal Auto Flow Valve
300 [2068]
20 Mesh Y Strainer Valve
600 [4137]
Flow switch - Low Pressure System
160 [1103]
Flow switch - High Pressure System
360 [2482]