CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tranquility
®
(TRL) Series
R e v. : N o v e m b e r 1 1 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
58
Unit Start-Up Procedure, Cont’d.
Motorized Water Valve Option Corrections
Model
Flow
Coefficient
(2Way) Cv
Max. Close-
Off Pressure
(MOPD)
WPD Adders
GPM
PSI
FT
TRL006
4.9
0 - 125 psi
1.50
0.09
0.21
1.88
0.15
0.35
2.25
0.21
0.49
TRL009
1.69
0.12
0.28
2.25
0.21
0.49
2.81
0.33
0.76
TRL012
2.25
0.21
0.49
3.00
0.37
0.85
3.75
0.59
1.36
TRL015
2.81
0.33
0.76
3.75
0.59
1.36
4.69
0.92
2.13
Table 9: TRL Braze Plate Water Pressure Drop
Model
U.S.
GPM
l/s
Pressure Drop, psi [kPa]
30°F [-1°C] 50°F [10°C] 70°F [21°C] 90°F [32°C]
006
1.5
0.09
1.4
0.6
0.4
0.5
1.88
0.12
2.0
0.9
0.6
0.7
2.25
0.14
2.5
1.1
0.8
1.0
009
1.69
0.11
1.9
1.4
1.3
1.3
2.25
0.14
2.9
2.5
2.3
2.3
2.8
0.18
4.0
3.6
3.3
3.3
012
2.25
0.14
2.6
2.2
2.0
1.9
3
0.19
4.3
3.8
3.5
3.4
3.8
0.24
6.0
5.4
5.0
4.9
015
2.8
0.18
3.3
2.7
2.5
2.5
3.8
0.24
5.6
5.0
4.8
4.7
4.7
0.30
7.8
7.1
6.9
6.8
⚠
WARNING!
⚠
⚠
CAUTION!
⚠
WARNING!
When the disconnect
switch is closed, high voltage is
present in some areas of the electrical
panel. Exercise caution when working
with energized equipment.
CAUTION!
Verify that ALL water
control valves are open and allow
water flow prior to engaging the
compressor. Freezing of the braze
plate or water lines can permanently
damage the heat pump.