CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Heat of Extraction (Absorption) or
Heat of Rejection =
flow rate (gpm)
x temp. diff. (°F)
x
fluid factor†
= (Btu/hr)
Superheat =
suction temp.
– suction saturation
temp.
= (°F)
Supercool =
discharge saturation
temp.
– liquid line temp.
= (°F)
† Use 500 for water, 485 for antifreeze.
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T ports to deter-
mine water flow and temperature difference. If water-side analysis shows poor performance, refrigerant troubleshooting
may be required. Connect refrigerant gauges as a last resort.